R55F Series Fiber-Optic Color Mark Sensors
Remote SETUP Mode
1) To enter SETUP mode, pulse once, wait 0.04 to 0.8 seconds, then pulse again.
2) Wait > 0.8 seconds, then enter sequential pulses to toggle between the six
output configuration choices (see page 7). Spacing between sequential pulses
must be > 0.8 seconds.
3) To exit SETUP mode, hold the TEACH input low for > 2 seconds.
Locking Out (Disabling) the Push Buttons
Pulse four times to disable (or to re-enable) the push buttons.
> 0.8 sec
Two pulses
to Enter
SETUP
Sequential
pulses to toggle
between configuration choices
T
T
T
T
etc.
> 0.8 sec
T
T
> 0.8 sec
Figure 8. SETUP mode
T
Pulse four times to enable
or disable push button
T
T
T
T
T
T
Figure 9. Push button lockout
R55F Series Sensor Dimensions
SETUP
DO
LO
OFF
Delay
Switch Point
+
DYNAMIC
–
STATIC
SETUP
DO
LO
OFF
Delay
Switch Point
+
DYNAMIC
–
STATIC
35.0 mm
(1.40")
11.6 mm
(0.46")
4.5 mm
(0.18")
12.9 mm
(0.51")
12.9 mm
(0.51")
30.0 mm
(1.18")
85.4 mm
(3.36")
24.5 mm
(0.97")
10.0 mm
(0.39")
Glass Fiber
Plastic Fiber
Quick-Disconnect
Models
Cabled
Models
10.0 mm
(0.39")
25.0 mm
(0.99")