R55F Series Fiber-Optic Color Mark Sensors
SETUP Mode
SETUP mode is used to configure sensor output response for:
- Light or Dark operate
- 20- or 40-millisecond pulse stretcher (OFF delay), if required.
It will be necessary to access SETUP mode only if the settings which result from
TEACH mode programming are not the settings required for the application. The
status LEDs indicate the output response configuration when the sensor is in RUN
mode, as follows:
- LO indicator ON = output is light operate
- DO indicator ON = output is dark operate
- OFF Delay indicator ON = either 20- or 40-millisecond delay is programmed
- OFF Delay indicator OFF = no output delay is programmed
To change the output response settings;
1)
Press and hold BOTH push buttons until the signal strength light bar turns OFF.
2)
Click EITHER push button to toggle through the six possible settings
indicated as follows:
SETUP
DO
LO
OFF
Delay
Switch Point
+
DYNAMIC
–
STATIC
Press and Hold
Both Push Buttons
Figure 3. SETUP mode
Output Configuration
Delay
Indicator
LO
Indicator
DO
Indicator
Light operate with no delay
OFF
ON
OFF
Light operate with 20 ms delay
Flashing
ON
OFF
Light operate with 40 ms delay
ON
ON
OFF
Dark operate with no delay
OFF
OFF
ON
Dark operate with 20 ms delay
Flashing
OFF
ON
Dark operate with 40 ms delay
ON
OFF
ON
3)
Press and hold both push buttons until the signal strength light bar turns ON,
indicating return to RUN mode.
NOTE: If SETUP mode programming is interrupted and remains inactive for 30
seconds, the sensor returns to RUN mode with the most recent settings
(i.e., exit and save current selection).