D12 Expert Series

page 

10

Self-diagnostics

D12 Expert sensors provide several self-diagnostic functions. One or more flashing
LEDs on the 7-segment display indicates a trouble condition. In addition, an alarm
output warns of marginal sensing conditions.

The D12 Expert’s 7-segment display indicates four problems:

Display: LED #7 flashes and green ON indicator is ON steadily. (Figure 6.)

Problem: The sensor flashes the #7 LED continuously and energizes the alarm output

when a marginal sensing condition develops during RUN mode. The
sensing area should be checked for any change which might affect the
received light level in either or both sensing conditions (for example, dirt
buildup on the sensing end of a fiber, misalignment of a fiber, or a change
in the target’s physical properties). If no changes can be identified, try 
re-teaching the sensor.

Display: LED #7 flashes and green ON indicator is OFF. (Figure 7.)

Problem: Load output is overloaded. Remove power, correct the problem, and 

re-apply power. Sensor will come up in RUN mode with the most recent
settings.

Display: LEDs #1 and 7 flash together, 6 times. (Figure 8.)

Problem: This occurs at the end of TEACH mode, when the sensor has received faulty

data. Faulty data may result from an unstable target or from high electrical
noise occurring while TEACH mode is in process. The sensor will return to
RUN mode, with the previous setting. Try re-teaching the sensor.

Display: LEDs #2 and 7 flash together. (Figure 9.)

Problem: These LEDs flash continuously to indicate a sensor component failure.

Return the sensor to the factory for replacement.

Figure 6. LED #7 flashes when a marginal

sensing condition develops.

ON

7

6

5

4

3

2

1

ALM

LO

DO

40 ms

0 ms

Indicator OFF

Indicator ON

Indicator Single-Flashing

Figure 7. LED #7 flashes with the power

indicator OFF; load output is
overloaded.

ON

7

6

5

4

3

2

1

ALM

LO

DO

40 ms

0 ms

Indicator OFF

Indicator ON

Indicator Single-Flashing

Figure 8. LEDs #1 and 7 flash together,

signaling faulty data.

ON

7

6

5

4

3

2

1

ALM

LO

DO

40 ms

0 ms

Indicator OFF

Indicator ON

Indicator Single-Flash 6 Times

Figure 9. LEDs #2 and 7 flash together,

signaling a sensor component
failure.

ON

7

6

5

4

3

2

1

ALM

LO

DO

40 ms

0 ms

Indicator OFF

Indicator ON

Indicator Single-Flashing

Summary of Contents for Expert D12 Series

Page 1: ...E2P6FP PNP sourcing IMPORTANT SEE SAFETY USE WARNING ON PAGE 4 D12 Expert Features Fiber optic sensors for DIN rail mounting 10 to 30V dc operation Visible red 680 nm light source models for use with...

Page 2: ...ming Modes TEACH Mode All photoelectric sensing applications excluding analog response applications involve differentiating between two received light levels The condition with the higher received lig...

Page 3: ...dels were first developed to ignore a small amount of web flutter in high speed registration color mark sensing applications At the end of the TEACH mode process the D12 Expert bargraph indicator flas...

Page 4: ...ontrast level and alarm Construction Black ABS Cycolac KJB housing with acrylic cover stainless steel M3 x 0 5 hardware for use with VALOX mounting bracket supplied the plastic fiber clamping element...

Page 5: ...Slide the fiber gripper up open For 010 or 020 dia fibers insert the small fiber adaptor into the ports as far as it will go B Insert the prepared plastic fiber sensor ends gently into the ports as fa...

Page 6: ...maximum sensitivity Use the following TEACH mode procedure at any time to return the sensitivity to its maximum setting Following the TEACH mode procedure on page 8 teach the following two conditions...

Page 7: ...nger Output settings are displayed Two steady red LEDs indicate the output settings light or dark operate and output timing 0 or 40ms NOTE The sensor continues to operate normally during the display p...

Page 8: ...l automatically return to RUN mode if the push button is not clicked within 10 seconds Double click ON indicator green LED single flashes at 1 Hz Green ON LED single flashes at 1Hz and the 7 segment d...

Page 9: ...ansistor The timing diagrams Figure 5 below define single double and triple click simulating the D12 Expert s programming push button The ON time of each click must be at least 40 milliseconds The min...

Page 10: ...n RUN mode with the most recent settings Display LEDs 1 and 7 flash together 6 times Figure 8 Problem This occurs at the end of TEACH mode when the sensor has received faulty data Faulty data may resu...

Page 11: ...For a complete selection of fibers in these sizes and for more information see your current Banner Photoelectric Sensors Catalog Qty Required for Each Unit 2 2 2 1 0 7 mm 027 individual pair IMM 443S...

Page 12: ...ge OPPOSED MODE 0 5 mm 02 bifurcated PBT26U 0 5 mm 02 individual pair PIT26U 84 mm 3 3 1 0 mm 04 individual pair PIT46U 315 mm 12 4 1 5 mm 06 individual pair PIT66U 660 mm 26 0 25 mm 1 0 1 0 mm 04 bif...

Reviews: