background image

E-Stop Safety Relay 

– Model ES-TA-3D1

4.5  Selecting the Autobaud Feature

The ES-TA-3D1 has an autobaud feature which allows for automatic recognition of the
baud rate on the network into which the ES-TA-3D1 is installed. This convenient
feature automatically matches the ES-TA-3D1 baud rate to the network without
requiring a baud rate configuration step. The autobaud feature is set to ON at the
factory. When the autobaud parameter is set to ON, the baud rate parameter may not
be set via the DeviceNet network. The autobaud parameter may be turned off by
setting the DeviceNet autobaud parameter to OFF (see the EDS file for path
information). When the autobaud parameter is set to OFF, the baud rate parameter
may be set via the DeviceNet network to the desired baud rate.

To determine if autobaud is set to ON, power (at the DeviceNet power inputs) the 
ES-TA-3D1 while it is not connected to the DeviceNet network; the Bus Status
Indicator will flash green, then red, then OFF in a repetitive sequence. If autobaud is
set to OFF, then the Bus Status Indicator will flash green (or red) after the initial
green/red sequence at power up.

4.6  Initial Checkout Procedure

1)

IMPORTANT: Ensure that there are no connections at terminals 39/19 and
40/20.

2) 

Close all E-stop inputs. Ensure all monitoring inputs are closed and that the
Reset input is open. (Refer to Figure 3.)

3)

Apply input power to the E-stop relay at terminals 1 and 21. Verify that K1,
K2 and Reset indicators are OFF. Verify that all E-stop and monitor indicators
are ON. (If Auto/Manual Reset selector is set to Auto mode, verify K1, K2
and all E-stop indicators are ON. Reset and all monitor indicators are OFF.)

4)

Close the Reset input (if Auto/Manual Reset selector is set to AUTO mode,
go to step 5). Verify that the Reset and K1 LED indicators go ON. K2
indicator should remain OFF. Open the Reset switch and verify that the Reset
indicator is OFF. The K1 and K2 indicators should both be ON at this time. If
the K2 indicator comes ON before the Reset switch is opened, disconnect
the input power and check all wiring. Return to step 2 after the cause of any
problem has been corrected. 

5)

Activate one Emergency Stop switch (open its contacts). The K1 and K2
indicators should turn OFF, simultaneously. If either indicator does not go
OFF, check the E-stop indicators. (The indicators for the activated Emergency
Stop switch should be OFF, as well as indicators for E-stops with higher
numbers. For example, if E-stop #3 is activated, the indicators for #3, #4, #5,
and #6 should all go OFF simultaneously.) If all E-stop indicators are OK but
either or both K1 and K2 indicators are ON, disconnect the input power and
check all wiring. Return to step 2 after the cause of the problem has been
corrected.

6)

Repeat the above checkout procedure for each E-stop switch, individually
(ES1 through ES6).

IMPORTANT . . .

Check Each Switch
Individually

Check ALL Emergency

Stop switches, individually, during
each checkout procedure. 
When two
or more Emergency Stop switches
are used, each switch must be
individually actuated (engaged), then
re-armed and the ES-TA-3D1 reset.
This allows the ES-TA-3D1 to check
each switch and its wiring to detect
faults.

!

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Summary of Contents for ES-TA-3D1

Page 1: ...its for a contact failure or wiring fault Diverse redundant input monitoring circuit DeviceNet monitoring of status and diagnostic information Auto reset or monitored manual reset Two output switching...

Page 2: ...y relay in any particular application are satisfied Extreme care is urged that all legal requirements have been met and that all installation and maintenance instructions contained in this manual are...

Page 3: ...ents The Emergency Stop switches become the inputs to the safety relay The safety relay monitors the condition of both contacts of each Emergency Stop switch connected to it The output of the safety r...

Page 4: ...on such as twisting pulling unlocking etc Additionally NFPA79 section 13 2 Emergency Stop Devices specifies the following switch stop control requirements Emergency stop pushbuttons shall be located a...

Page 5: ...hardware Leave a minimum 1 cm 1 4 gap between the module housing and other adjacent housings to allow room for potential board replacement at a later date The ES TA 3D1 E Stop Safety Relay control mo...

Page 6: ...witch The circuit Reset switch can be any mechanical switch such as a normally open momentary switch a two position key switch etc The Reset switch must meet the requirements listed in the Product Spe...

Page 7: ...R install suppressors directly across the output contacts of the ES TA 3D1 safety relay It is possible for suppressors to fail as a short circuit If installed directly across the output contacts of th...

Page 8: ...ches are above 63 and the current address of the ES TA 3D1 as recognized by the DeviceNet controller was set with the MAC ID address rotary switches above 63 4 4 Selecting Auto or Manual Reset Mode Th...

Page 9: ...ON If Auto Manual Reset selector is set to Auto mode verify K1 K2 and all E stop indicators are ON Reset and all monitor indicators are OFF 4 Close the Reset input if Auto Manual Reset selector is se...

Page 10: ...Safety Relay should be mounted inside a lockable enclosure For security reasons the key to the lockable enclosure must be in the possession of a Qualified Person or Persons A Qualified Person is a per...

Page 11: ...action is not necessary The machine must not start at this point Initiate the machine startup procedure per manufacturer s instructions Verify that the machine restarts in correct sequence 3 Repeat t...

Page 12: ...mple the indicator lights for ES3 ES4 ES5 and ES6 will come back ON K1 and K2 will close and their LED indicators will come ON 1 After the Reset switch is closed and then opened Manual Reset mode or 2...

Page 13: ...F For example if switch 4 has been activated the indicators for switches 4 5 and 6 will be OFF To reset start by verifying that the problem prompting the E stop procedure has been corrected The E stop...

Page 14: ...DeviceNet network is properly terminated and grounded per DeviceNet specifications 4 Check for insufficient network power supply Red Flashing Connection timeout or no power to ES TA 3D1 1 Check input...

Page 15: ...rying the cover open Figure 11 The cover is not hinged it will come completely off 3 Gently push the sides of the module housing outward at the top corners to dislodge the four locking tabs on the two...

Page 16: ...to fully engage the tabs into their slots 4 Remount the module and replace the wiring barriers by pushing them down into their receptacles Take care to match the terminal labels on the wiring barriers...

Page 17: ...Specifications Bus Status Indicator A bi colored red green LED visible on the control module indicates network status Green Steady On line connected allocated to master Flashing On line not connected...

Page 18: ...ion size of 0 bytes Assembly instance 2 is used as the response data for the COS command A COS command is issued in response to a change in the E stop relay operating mode Produced connection size of...

Page 19: ...input is known 1 The status of the reset input is unknown disabled Reset Input 0 The reset input is open 1 The reset input is closed K1 Relay Invalid 0 The state of the K1 relay is known 1 The state o...

Page 20: ...life 100 000 at full resistive load NOTE Transient suppression is recommended when switching inductive loads Install suppressors across load Never install suppressors across output contacts see Warni...

Reviews: