Banner ES-TA-3D1 Manual Download Page 11

E-Stop Safety Relay 

– Model ES-TA-3D1

5.2  Periodic Checkout Requirements 

The functioning of the Emergency Stop system (including the ES-TA-3D1 E-Stop
Safety Relay and the guarded machine) must be verified on a regular periodic basis to
ensure proper operation (see also the machine manufacturer’s recommendations). 

Procedure:

1) With the machine running, activate one Emergency Stop switch, (open its

contacts). Verify that the machine stops. (The K1 and K2 indicators should turn
OFF, simultaneously. If either indicator does not go OFF, check the E-stop
indicators. The indicators for the activated Emergency Stop switch should be OFF,
as well as indicators for E-stops with higher numbers. For example, if E-stop #3
is activated, the indicators for #3, #4, #5, and #6 should all go OFF
simultaneously.) If all E-stop indicators are OK but either or both K1 and K2
indicators are ON, disconnect the input power and check all wiring. Repeat this
step after the cause of any problem has been corrected.

2) Return the Emergency Stop switch to its closed-contact position. Close and open

the Reset switch (if the controller is in Auto Reset mode, this action is not
necessary). The machine must not start at this point. Initiate the machine startup
procedure (per manufacturer’s instructions). Verify that the machine restarts in
correct sequence.

3) Repeat the above checkout procedure for each E-stop switch, individually (ES1

through ES6).

5.3 Normal Operation 

Following are examples of LED status indication and DeviceNet information for typical
ES-TA-3D1 RUN, STOP, and FAULT conditions.

5.3.1  RUN Condition

The following LED status represents a normal run condition, where all E-stop
switches are closed, and the E-stop relay has been reset so that K1 and K2 output
contacts are closed:

ES4

A

B

ES3

A

B

ES2

A

B

ES1

24V

DC

+

PWR

A

B

ES5

A

B

ES6

RESET

A

B

MONITOR

1

2

3

K1

K2

4

Indicator Key

Indicator "ON"

Indicator "OFF"

Figure 7. Indicator status for normal RUN condition

Operating mode: OK (Go)

E-stop Inputs:

All Closed

Monitor Inputs:

Mon 1 Open
(NOTE: unused,
jumpered monitor
contacts will not be
listed as open)

Reset Mode:

Manual Reset
(or Auto Reset,
depending on selection)

Reset Input:

- - - - - -
(or Disabled if in Auto
Reset mode)

K1 Relay:

Energized

K2 Relay:

Energized

Autobaud:

On (or Off, depending on
selection)

Fault Type:

No Fault

Action 1:

- - - - - -

Action 2:

- - - - - -

Action 3:

- - - - - -

A normal RUN condition is reported to
DeviceNet as follows:

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Summary of Contents for ES-TA-3D1

Page 1: ...its for a contact failure or wiring fault Diverse redundant input monitoring circuit DeviceNet monitoring of status and diagnostic information Auto reset or monitored manual reset Two output switching...

Page 2: ...y relay in any particular application are satisfied Extreme care is urged that all legal requirements have been met and that all installation and maintenance instructions contained in this manual are...

Page 3: ...ents The Emergency Stop switches become the inputs to the safety relay The safety relay monitors the condition of both contacts of each Emergency Stop switch connected to it The output of the safety r...

Page 4: ...on such as twisting pulling unlocking etc Additionally NFPA79 section 13 2 Emergency Stop Devices specifies the following switch stop control requirements Emergency stop pushbuttons shall be located a...

Page 5: ...hardware Leave a minimum 1 cm 1 4 gap between the module housing and other adjacent housings to allow room for potential board replacement at a later date The ES TA 3D1 E Stop Safety Relay control mo...

Page 6: ...witch The circuit Reset switch can be any mechanical switch such as a normally open momentary switch a two position key switch etc The Reset switch must meet the requirements listed in the Product Spe...

Page 7: ...R install suppressors directly across the output contacts of the ES TA 3D1 safety relay It is possible for suppressors to fail as a short circuit If installed directly across the output contacts of th...

Page 8: ...ches are above 63 and the current address of the ES TA 3D1 as recognized by the DeviceNet controller was set with the MAC ID address rotary switches above 63 4 4 Selecting Auto or Manual Reset Mode Th...

Page 9: ...ON If Auto Manual Reset selector is set to Auto mode verify K1 K2 and all E stop indicators are ON Reset and all monitor indicators are OFF 4 Close the Reset input if Auto Manual Reset selector is se...

Page 10: ...Safety Relay should be mounted inside a lockable enclosure For security reasons the key to the lockable enclosure must be in the possession of a Qualified Person or Persons A Qualified Person is a per...

Page 11: ...action is not necessary The machine must not start at this point Initiate the machine startup procedure per manufacturer s instructions Verify that the machine restarts in correct sequence 3 Repeat t...

Page 12: ...mple the indicator lights for ES3 ES4 ES5 and ES6 will come back ON K1 and K2 will close and their LED indicators will come ON 1 After the Reset switch is closed and then opened Manual Reset mode or 2...

Page 13: ...F For example if switch 4 has been activated the indicators for switches 4 5 and 6 will be OFF To reset start by verifying that the problem prompting the E stop procedure has been corrected The E stop...

Page 14: ...DeviceNet network is properly terminated and grounded per DeviceNet specifications 4 Check for insufficient network power supply Red Flashing Connection timeout or no power to ES TA 3D1 1 Check input...

Page 15: ...rying the cover open Figure 11 The cover is not hinged it will come completely off 3 Gently push the sides of the module housing outward at the top corners to dislodge the four locking tabs on the two...

Page 16: ...to fully engage the tabs into their slots 4 Remount the module and replace the wiring barriers by pushing them down into their receptacles Take care to match the terminal labels on the wiring barriers...

Page 17: ...Specifications Bus Status Indicator A bi colored red green LED visible on the control module indicates network status Green Steady On line connected allocated to master Flashing On line not connected...

Page 18: ...ion size of 0 bytes Assembly instance 2 is used as the response data for the COS command A COS command is issued in response to a change in the E stop relay operating mode Produced connection size of...

Page 19: ...input is known 1 The status of the reset input is unknown disabled Reset Input 0 The reset input is open 1 The reset input is closed K1 Relay Invalid 0 The state of the K1 relay is known 1 The state o...

Page 20: ...life 100 000 at full resistive load NOTE Transient suppression is recommended when switching inductive loads Install suppressors across load Never install suppressors across output contacts see Warni...

Reviews: