2. Write a 10 to Modbus register 4151
To reset only the I/O board:
1. Write a 0 to Modbus register 4152
2. Write a 10 to Modbus register 4151
Modbus Register
Values
Description
4151
0–255
Reset/restore trigger. This timer is based in 100 millisecond units. Once written, the timer starts to count down to
zero. After the timer expires, the restore factory defaults are applied if register 4152 = 1. If register 4152 is zero, the
I/O board is reset.
Default value: 0
1 = 100 milliseconds, 10 = 1 second.
4152
0–1
1 = Restores factory defaults for I/O parameters.
Default value: 0
DXM150-Sx Wireless Modbus Slave
36