Modbus Registers for the I/O Board
The I/O board is Slave ID 11.
Base Board Input Connection
Modbus Register
Description
1
Optically isolated input 1
2
Optically isolated input 2
3
Universal input 1
4
Universal input 2
5
Universal input 3
6
Universal input 4
7
Universal input 5
8
Universal input 6
9
Universal input 7
10
Universal input 8
Base Board Output Connection
Modbus Register
Description
501
PNP/NPN Output 1
502
PNP/NPN Output 2
503
PNP/NPN Output 3
504
PNP/NPN Output 4
505
PNP/NPN Output 5
506
PNP/NPN Output 6
507
PNP/NPN Output 7
508
PNP/NPN Output 8
509
DAC Output 1
510
DAC Output 2
Configuration Registers for the I/O Board
The DXM Configuration Tool creates a graphical view of the I/O board parameters. This allows for easy and quick
configuration of the I/O board parameters. Modbus configuration registers are identified below.
Register
Isolated Input A
3013
Enable rising edge counter
3014
Enable falling edge counter
3015
High register for counter
3016
Low register for counter
Register
Isolated Input A
3033
Enable rising edge counter
3034
Enable falling edge counter
3035
High register for counter
3036
Low register for counter
Universal Input Parameter Modbus Registers
Universal Inputs
1
2
3
4
5
6
7
8
Enable Full Scale
3303
3323
3343
3363
3383
3403
3423
3443
Temperature °C/°F
3304
3324
3344
3364
3384
3404
3424
3444
Input Type
3306
3326
3346
3366
3386
3406
3426
3446
Threshold
3308
3328
3348
3368
3388
3408
3428
3448
Hysteresis
3309
3329
3349
3369
3389
3409
3429
3449
Enable Rising
4908
4928
4948
4968
4988
5008
5028
5048
Enable Falling
4909
4929
4949
4969
4989
5009
5029
5049
High Register for Counter
4910
4930
4950
4970
4990
5010
5030
5050
Low Register for Counter
4911
4931
4951
4971
4991
5011
5031
5051
Enable Full Scale. Set to 1 to enable a linear range from 0 to 65535 for specified input range. For a 4 to 20 mA input, a value
of 0 represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store input readings in unit-specific data. For
example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA inputs), values are
stored as µA (micro Amps) and voltage values are stored as mV (millivolts).
DXM150-Sx Wireless Modbus Slave
www.bannerengineering.com - Tel: +1.763.544.3164
33