4.5.2 Relay Outputs
Pin
Output
Description
Wiring
Pin 19
Output 1: Normally Open
SPDT (Form C) relay, 250 V ac, 16 A
Normally open
Common
Normally closed
Pin 20
Output 1: Common
Pin 21
Output 1: Normally Closed
Pin 22
Output 3: Normally Open
Pin 23
Output 3: Common
Pin 24
Output 3: Normally Closed
4.5.3 NMOS Outputs
Pin
Output
Description
Wiring
Pin 25
NMOS Discrete
Outputs
Less than 1 A maximum current at 30 V dc
ON-State Saturation: Less than 0.7 V at 20 mA
ON Condition: Less than 0.7 V
OFF Condition: Open
Output
Pin 27
Pin 28
Pin 30
4.5.4 Analog Outputs (DAC)
The following characteristics are configurable for each of the analog outputs.
Pin
Output
Description
Pin 33
Analog Output 1
0 to 20 mA or 0 to 10 V dc output (I/O board jumper selectable)
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
Pin 32
Analog Output 2
Parameters for Analog Output 1 start at 4001 through 4008. Parameters for Analog Output 2 start at 4021 through 4028.
Parameter Registers for Analog Outputs (4xxxx)
OUT 1
OUT 2
Parameters
4001
4021
Maximum Analog Value
4002
4022
Minimum Analog Value
4003
4023
Enable Register Full Scale
4004
4024
Hold Last State Enable
4005
4025
Default Output State
4008
4028
Analog Output Type
Analog Output Type. The analog outputs may be configured as either 0 to 20 mA outputs (default) or 0 to 10 V outputs. To
change the analog output type change the hardware jumper position and write to the Modbus register that defines the
analog output type. For analog output 1, write to Modbus register 4008, for analog output 2 write to Modbus register 4028.
Write a value of 2 (default) to select 0 to 20 mA; write a value of 3 to select 0 to 10 V.
Default Output Conditions. Default output conditions/triggers are the conditions that drive outputs to defined states.
Example default output conditions include when radios are out of sync, when a device cycles power, or during a host
communication timeout.