Calibration SET
• Sets a threshold exactly at the presented condition
• Threshold can be adjusted using “+” and “-” rocker button (Manual Adjust)
A single sensing condition is presented, and the sensor positions a threshold exactly at the presented condition. When a condition lighter
than the threshold is sensed, the output either turns ON or OFF, depending on the LO/DO switch setting (see LO/DO Switch in
on page 2).
Sensor positions
threshold exactly at
the presented condition
Threshold position
adjusted by
Manual Adjust
Darkest
(no signal)
Most Light
(saturated
signal)
Output OFF
Output ON
Condition
Presented
Figure 11. Calibration SET (Light Operate shown)
Calibration SET and Manual Adjust
• Moves switching threshold value up or down to make adjustments
• Slide Mode switch to ADJ to enter Adjust mode
• Press “+” to increase; press “-” to decrease
• GREEN display shows the switching threshold value
• 2 seconds after adjustment, the GREEN display will flash 3 times to confirm
• Slide Mode switch to RUN to complete operation
Remember: Auto Thresholding is automatically disabled in Calibration SET
DF-G1 - Expert Dual Display Fiber Amplifier Manual