July 17, 2023
Asset Monitoring Gateway With SNAP ID Instruction Manual
14
Sensor Specific Settings
Applies to two generic analog Modbus converters: S15C-I-MQ 4-20mA and S15C-U-MQ 0-10Vdc.
Special Settings 1
In this example, the special scaling is set for a 420mA current converter that is monitoring a 0600mm LASER distance
sensor (such as the Q4X series from Banner Engineering).
Select a sensor in the table to reveal a button to access the special scaling for that model.
Toggle Custom Scaling
to
ON.
In our example, the units to mm, the converter input range in mA to 4mA and 20mA, and the value range to 0 to 600 mm.
Press
Save
and confirm. The change is saved to the device locally and is stored to display in the sensor's statistics and
data in all menus.
Sensor Custom Scaling
IMPORTANT: If you need to push sensor-specific data to Banner Cloud Data Services, you must also
configure the custom scaling in the cloud because the AMG only stores this data locally.
Initialize the VIBE-IQ Machine Learning Algorithm
After global settings have been confirmed in the special settings window, previously commissioned vibration sensors can acti
vate VIBEIQ from the
Utilities
›
Sensor List
›
Thresholds
screen or the
Groups
›
Sensor Values
›
Thresholds
screen,
and select the corresponding threshold for the specific sensor.
By default, the thresholding method is set to
real-time
to allow a user to manually configure known thresholds for the sensor.