Installation and wiring
•
The device is only permitted to be operated in closed rooms and not permitted to be exposed to direct
sunlight.
•
The climatic and ambient conditions must be taken into account –
see "Environmental properties" on page
.
General installation instructions
•
When installing the device, the permissible mounting orientations must be observed - .
•
When connecting installed or connected peripherals, follow the instructions in the peripheral device's doc-
umentation.
Transport and storage
When transporting at low temperatures or in the event of large temperature fluctuations, the collection of moisture
in or on the device is not permitted. Moisture can cause short circuits in electrical circuits and damage the device.
If a device is transported or stored without packaging, all environmental influences such as shocks, vibrations,
pressure and moisture have an unprotected effect on the device. Damaged packaging indicates that the device
has been severely affected by environmental influences and may have been damaged.
This can result in malfunctions of the device, machine or system.
Use of third-party products
If third-party devices or components are used, the relevant manufacturer's documentation must be observed. If lim-
itations or interactions by or with third-party products are possible, this must be taken into account in the application.
5.2 Requirements for the installation cutout
When installing the Power Panel, it is important to ensure that the surface and wall thickness meet the following
conditions:
Installation cutout property
Value
Permissible deviation from evenness
Note:
This condition must also be observed when the device is installed.
≤0.5 mm
Permissible surface roughness in the area of the gasket
≤120 µm (Rz 120)
Min. wall thickness
2 mm
Max. wall thickness
6 mm
1)
1)
A derating of the ambient temperature of 5°C must be taken into account for all mounting orientations and diagonals starting at a wall thickness greater than
4 mm (see
"Derating the ambient temperature" on page 28
).
Notice!
The degree of protection of the device (see technical data) can only be maintained if the device is
installed in an appropriate housing with at least the same degree of protection per the above require-
ments.
Notice!
The device must ultimately be installed in a protective housing with sufficient rigidity (per UL 61010-1
and UL 61010-2-201).
5.2.1 Installation cutout
Information:
When installing, spacing for air circulation and additional free space for operating and servicing the
device must be taken into account.
Power Panel C80 User's manual V1.02
37