Device description
4.7.8 Ethernet interface (IF2)
ETH1
Variant
RJ45, female
Controller
Intel I210
Wiring
S/STP (Cat 5e)
Transfer rate
10/100/1000 Mbit/s
1)
Cable length
Max. 100 m (min. Cat 5e)
LED "Speed" (a)
On
Off
Green
100 Mbit/s
10 Mbit/s
2)
Orange (dark)
1000 Mbit/s
-
LED "Link" (b)
On
Active
Orange (light)
Link (a connection to an
Ethernet network exists)
Blinking (data be-
ing transferred)
1)
Switching takes place automatically.
2)
The 10 Mbit/s transfer rate / connection is only available if LED "Link" is active at the same time.
Information:
This Ethernet interface (IF2) is not suitable for POWERLINK.
4.7.9 POWERLINK interface (IF1)
Figure
Pinout
Terminal
Ethernet
1
RXD
Receive data
2
RXD\
Receive data\
3
TXD
Transmit data
4
Termination
5
Termination
6
TXD\
Transmit data\
7
Termination
8
Termination
Diagnostic LED status indicators
LED
Color
Status
Description
Link
LNK (a)
Green
On
Link established to an Ethernet network.
Activity
On
No Ethernet activity taking place.
ACT (b)
Orange
Blinking
Ethernet activity taking place (data being
transferred).
POWERLINK V2 mode
By default, the POWERLINK interface is operated as a managing node (MN). In the managing node, the node
number is set to a fixed value of 240.
If the POWERLINK node is operated as a controlled node (CN), a node number from 1 to 239 can be set in the
POWERLINK configuration in Automation Studio.
Ethernet mode
In this mode, the interface is operated as an Ethernet interface. The INA2000 station number is set using the B&R
Automation Studio software.
Information:
If interface IF1 is operated in Ethernet mode, then this interface receives its own IP address and works
independently of Ethernet interface IF2.
Power Panel C80 User's manual V1.02