Installation and wiring
152
Automation Panel 5000 User's manual V2.11
5.5.4 Removing the swing arm mounting unit
The mounting unit can be rotated 180°, which makes it possible to install on a swing arm system from above or
below.
The following requirements must be met:
•
All connected cables must be disconnected.
•
The Automation Panel must no longer be installed on the VESA or swing arm system.
1. Disconnect the power supply cable to the Automation Panel (disconnect the power cable!). Disconnect from
all sources and poles!
2. Carry out electrostatic discharge at the ground connection.
3. Place the Automation Panel on a clean, flat surface.
4. Remove the mounting unit cover by following the steps provided in section
.
5. Remove the 8 Torx screws used to fasten the mounting unit to the Automation Panel (T25: 2x M5x65, 6x
M5x12).
Caution!
Loss of impermeability
•
The gasket must be inspected before installation or reinstallation and at regular intervals
according to the requirements of the operating environment.
•
Replace the entire device if inspection reveals visible scratches, cracks, dirt deposits or
excessive wear.
•
Do not stretch the gasket unnecessarily.
•
Avoid contact between the gasket and the corners and edges of the frame.
•
It is important to ensure that the gasket is completely inserted into the installation notch.
•
The housing components must be secured using the specified tightening torque.
Failure to follow these instructions can result in damage to property.
Warning!
The M5x65 screws are equipped with a special screw locking mechanism and only designed to
be used once. New screws must be used if removing and reinstalling.