Technical data • Individual components
114
Panel PC 2100 swing arm user's manual V1.12
3.4.6 5ACCIF01.FPSC-000
3.4.6.1 General information
Interface option 5ACCIF01.FPSC-000 is equipped with a POWERLINK, RS232 and CAN bus master interface. 32
kB of FRAM is also installed.
•
1x POWERLINK interface managing or controlled node
•
1x CAN bus master interface
•
1x RS232 interface
•
32 kB FRAM
•
Compatible with the APC2100 and PPC2100
This interface option can only be operated with Automation Runtime.
3.4.6.2 Order data
Model number
Short description
Figure
Interface options
5ACCIF01.FPSC-000
Interface card - 1x RS232 interface - 1x CAN interface - 1x POW-
ERLINK interface - 32 kB FRAM - For APC2100/PPC2100 - On-
ly available with a new device
Optional accessories
Terminal blocks
0TB1210.3100
Connector 300 VDC - 10-pin female - Cage clamp terminal block
- Protected against vibration by the screw flange
Table 123: 5ACCIF01.FPSC-000 - Order data
3.4.6.3 Technical data
Information:
The following characteristics, features and limit values only apply to this accessory and can deviate
from those specified for the complete system. The data specifications for the complete system take
precedence over those of individual components.
Model number
5ACCIF01.FPSC-000
General information
LED status indicators
L1, L2, L3
B&R ID code
0xE53F
Certification
CE
Yes
UL
cULus E115267
Industrial control equipment
HazLoc
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
1)
DNV GL
Temperature:
B
(0 - 55°C)
Humidity:
B
(up to 100%)
Vibration:
A
(0.7 g)
EMC:
B
(Bridge and open deck)
2)
Controller
FRAM
Size
32 kB
Remanent variables in power failure mode
32 kB
(for e.g. Automation Runtime, see Automation Help)
Interfaces
COM
Quantity
1
Type
RS232, not modem-capable, not electrically isolated
Design
10-pin, male
UART
16550-compatible, 16-byte FIFO
Max. baud rate
115 kbit/s
POWERLINK
Quantity
1
Transmission
100BASE-TX
Type
Type 4
3)
Design
Shielded RJ45
Transfer rate
100 Mbit/s
Cable length
Max. 100 m between two stations (segment length)
Table 124: 5ACCIF01.FPSC-000 - Technical data