Description:

Alarm panel connections:
- 12 V supply: possibly through fuse 1 AT.
- Monitoring output: the output relay is open as long as the alarm panel is

not

 

monitoring and closed as long as it is in monitoring mode.

- Alarm output: the output relay is open as long as the alarm panel is not 

in an

 

alarm condition and switches to closed when in alarm.

- Tamper: Tamper is detected when the loop is interrupted.

- Dialler input 1: OKout output: Technical failures / problems are

 

reported

to the dialler when 

NO

 contact opens.

- Dialler input 2: Empty fog cartridge or "no power to

 

fog generator".

Both problems are reported together to the dialler when one or both  

NO

 contact ([Empty] or [Power]) opens.

PIR Confirmation sensor:

A typical PIR or better dual-technology (PIR / radar) sensor.
Objective: To delay the alarm status until a local zone detector confirms the 
burglary signal of the alarm locally. The connected PIR / radar detector will 
then open its contacts and the 12 VDC

 

on the confirmation input [Conf.] is 

removed, and consequently the alarm mode is

 

confirmed.

Dip switch settings:

 Dip G: is 

ON

 = the controller and the fog generator

are in monitoring mode [Guard] as long as there is 
12 

VDC

 provided to the Guard input [Guard]

.

When 

the controlling alarm system's

 

monitoring contact closes, 

the orange Guard LED will light
and 

BANDIT

 is in monitoring status            

.

Dip A: is 

ON

 = the controller and the fog generator 

are in alarm mode

(Incl. fog ejection) as long as there is 12VDC provided to the alarm 
input [Alarm]. 
So when the alarm system closes its alarm contact, the orange Alarm 
LED will light and 

BANDIT

 is in the alarm status until removal of the 

monitoring status.

Dip C: 

is 

OFF

 

=

 

when the connected sensor remains inactive, its alarm 

contacts are closed, so there is 12 

VDC

 on the Confirmation

input [Conf.] and the orange LED Conf. is lit
When the sensor detects motion, it opens its alarm contacts
and so removes

 

the 12 

 over [Conf.], so confirmation to

VDC

switch to the alarm mode. 

Conf.

C+

C-

Alarm

A+

A-

Guard

G+

G-

1 2 3 4

1 2 3

1 2

1 2 3 4

1 2 3

1 2

Front 

Inputs

G A C F

2 3

X

1

1 2 3 4

1 2 3

1 2

Guard

Guard

BANDIT

 

Controller CF31 v2

 

/ Manual v.102

Installation example 2 - p. 35

Summary of Contents for CF31

Page 1: ...V Error VDC 12 11 14 vdc Guard Alarm Conf G A C G C Fire F F Power no com OK nc no Tamper com Empty no com no com PanBut Inputs Outputs A Alarm Guard Panic Fog isolation Fog control Force ejection Gu...

Page 2: ...inputs Panic input Outputs Communication with fog generator Settings via Dip switches Information concerning inserted cartridges Status and Malfunction indicator Fog ejection blocking and forcing Cla...

Page 3: ...wired communication cable between Fog generator and controller Modular setup Example Fog generator BANDIT 320 V 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 S ta tu s A la rm G ua rd P an ic B...

Page 4: ...me HY 3 is a registered tradename The BANDIT fog generator process is internationally protected by various patents Manufacturer BANDIT nv plc RPR Antwerp div Tongeren Nijverheidslaan 1547 Tel 32 89 85...

Page 5: ...12 11 14 vdc Guard Alarm Conf G A C G C Fire F F Power no com OK nc no Tamper com Empty no com no com PanBut Inputs Outputs A Alarm Guard Panic Fog isolation Fog control Force ejection Guard Alarm G...

Page 6: ...supply voltage is too high 14 4 volts At a supply voltage of 18 volt an internal overvoltage overcurrent protection will trip return to factory and with no warranty All control inputs are equipped wit...

Page 7: ...he duration the fog generator is in monitoring mode Guard state the Front LED error flashing is inhibited so that it will never indicate the presence of any failure or problem Properties of the monito...

Page 8: ...jection see next page 7 confirmation and page 12 Flowchart Properties of the alarm status The orange LED Alarm will be illuminated in the section Status as long as the device is in alarm mode The fron...

Page 9: ...ed to the BANDIT The purpose of this feature is to postpone proceeding to alarm mode until a local zone or intrusion detector confirms the burglary Features of the confirmation input Conf The BANDIT c...

Page 10: ...le cannot start including through the Force ejection button Control of the fire input Fire Depending on the position of dip switch F Fire mode will be active either when 12 VDC is present on the input...

Page 11: ...rast to the four control inputs this input is not a 12 VDC voltage controlled input This input has two setting modes via dip switch setting PanBut 1 a NO or NC contact input The input monitors whether...

Page 12: ...the contact is open Panic mode a Dip 3 OFF stop one minute after the first pulse is received 1 minute delay timer or b Dip 3 ON last as long as the contact is closed PanBut Comm p 10 Panic input Advan...

Page 13: ...3 1 2 3 Dip switch settings PanBut Dip 1 ON Dip 2 and 3 a No backlight Dip 2 OFF and Dip 3 OFF b 50 dimmed backlighting Dip 2 ON and Dip 3 OFF c 100 of backlight Dip 2 ON and Dip 3 ON Panic mode star...

Page 14: ...ut Confirm input Fire input Yes active Yes active Yes active Yes active Yes active Not active Not active Fog ejection 2 3 4 5 23 6 24 Guard Panic Fog isolat Internal buzzer fog generator Voltage input...

Page 15: ...nerator illuminates orange 7 Output Monitoring Guard Guard nc no com Guard During monitoring COM and NO is closed OUTPUTS All six outputs are represented by potential free relay contacts This will pro...

Page 16: ...r alarm mode 4In case of alarm mode COM and NO are closed relay activated from the start of the alarm mode for 3 minutes reset timer If the alarm mode is interrupted Monitoring mode is switched OFF th...

Page 17: ...munication error is detected between the controller and the fog generator Possible causes None or poor electrical connection between the three terminal connectors Fog on the controller and the corresp...

Page 18: ...gisters any movement or twisting of the fog generator and sends notification of this abnormality to its controller The motion sensitivity is adjustable via 2 DIP switches Move see p 25 Normally this T...

Page 19: ...output OK is displayed on the Controller panel Signals to check a If any red LED is lit then this also indicates the problem that has been detected b If any red LED is flashing eg Error LED then this...

Page 20: ...t LED of the BANDIT fog generator will flash red in order to indicate that there is a problem For more information see p 26 This fog cartridge output Empty may be used in conjunction with the OK outpu...

Page 21: ...e that there is a problem This output Power may be used in conjunction with the OK output or on its own see example diagram 1 on page 32 to connect this notification to a zone input of the controlling...

Page 22: ...tro l For ce ejec tion Ala rm A Fo g nc Cov er Mo ved Pan But To Fog Tam per Re set Com m Dip cha nge Rea d dips nc no com Gua rd no com Ala rm nc 1 2 3 Co mm G A C F 2 3 1 2 3 X Y 1 1 2 3 4 1 2 3 1...

Page 23: ...he electrical connection Controller fog generator has been installed correctly Fog LED b The controller has 12VDC power supply 12 VDC LED green To enter new identification data press the Comm key Resu...

Page 24: ...terminals OFF Alarm mode is starts when 0 V no voltage is on Alarm terminals Dip C Configuration of confirmation input Conf ON Confirmation is provided when 12 V is on Conf terminals OFF Confirmation...

Page 25: ...FF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON 40 60 m 160 180 60 80 80 100 100 120 140 160 180 200 120 140 Set up table Fog volume of the area M Setting example To ensure fog ejection...

Page 26: ...ridge in any case Of course the result will not meet the stated expectations for filling the volume because there may be not enough or too much fog produced For more information about how to set the f...

Page 27: ...so Example diagram 3 on p 36 1 2 3 1 2 3 PanBut 1 2 3 1 2 3 Block Motion control Move The BANDIT fog generator is internally equipped with a motion sensor solid state gyroscope This sensor detects whe...

Page 28: ...hat the fog generator always has two full cartridges so as to maintain maximum security in the event of two consecutive burglaries or robberies Dispose of the empty cartridge responsibly in ordinary m...

Page 29: ...s and fault indication p 27 The heat exchanger is at normal operating temperature OK Monitoring mode Guard Front LED As long as the fog generator is connected in monitoring status Guard by its control...

Page 30: ...he yellow attention button on the panic button is pushed See also p 9 and 10 This yellow LED lights as long as the beeper beeps This yellow LED lights up as long as the fog generator monitoring mode i...

Page 31: ...d via the red LED otherwise there is no indication to show this abnormal setting all other functions outputs and LED s operate on the controller as normal The purpose of this fog isolation option is t...

Page 32: ...make sure you have a replacement To comply with security industry good practice and professionalism always conduct a full system test after the installation of a system to confirm its correct operati...

Page 33: ...P security level is defined in the following table Which grade suits at what maximum volume of a space is indicated by the manufacturer or importer in the specifications of the fog generator eg Grade...

Page 34: ...o com PanBut PanBut Inputs Outputs A Alarm Guard Panic Fog isolation Fog control Force ejection Guard Alarm G A G A Panic Fog isolation Fog control Force ejection Alarm A Fog nc Cover Moved PanBut To...

Page 35: ...g contact closes the orange Guard LED will light and BANDIT is in monitoring mode Dip A is ON the controller and the fog generator are in alarm mode Incl fog ejection as long as there is 12 VDC provid...

Page 36: ...Outputs A Alarm Guard Panic Fog isolation Fog control Force ejection Guard Alarm G A G A Panic Fog isolation Fog control Force ejection Alarm A Fog nc Cover Moved PanBut To Fog Tamper Reset Comm Dip c...

Page 37: ...on input Conf is removed and consequently the alarm mode is confirmed Dip switch settings Dip G is ON the controller and the fog generator are in monitoring mode Guard as long as there is 12 VDC provi...

Page 38: ...og control Force ejection Guard Alarm G A G A Panic Fog isolation Fog control Force ejection Alarm A Fog nc Cover Moved PanBut To Fog Tamper Reset Comm Dip change Read dips nc no com Guard no com Alar...

Page 39: ...1 2 3 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 Front Inputs M Move PanBut G A C F 2 3 1 2 3 X Y 1 1 2 3 4 1 2 3 1 2 3 1 2 3 Settings Once Dip PanBut 1 is read as ON the controller will assume that there...

Page 40: ...rd Alarm G A G A Panic Fog isolation Fog control Force ejection Alarm A Fog nc Cover Moved PanBut To Fog Tamper Reset Comm Dip change Read dips nc no com Guard no com Alarm nc 1 2 3 Comm G A C F 2 3 1...

Reviews: