SECTION 6: DUCT HEATER INSTALLATION
6.1 General
To connect the inlet and o
u
tlet d
u
cts to the heater,
D
u
ct-Mate or similar flanges may be slid over the
d
u
ct connector flanges s
u
pplied on the
u
nit and
sec
u
red
w
ith scre
w
s. The connection to the d
u
ct
then can be made
u
sing the D
u
ct-Mate clips. The
d
u
cts m
u
st have removable access panels
u
pstream and do
w
nstream of the heater. These
panels m
u
st be of appropriate size and placement
so that smoke or reflected light co
u
ld be observed to
indicate the presence of leaks in the heat
exchanger. Covers for these openings sho
u
ld be
sealed to prevent leakage.
Any transition into the inlet of the heater sho
u
ld be
smooth,
w
ith a taper of no more than 15 degrees. If
elbo
w
s are req
u
ired, they sho
u
ld be of either broad
radi
u
s or fitted
w
ith properly designed air t
u
rns.
Cons
u
lt a professional to ens
u
re air t
u
rns are
properly designed.
The heater m
u
st be installed on the positive
press
u
re side of the circ
u
lating air blo
w
er. Air flo
w
thro
u
gh the heater m
u
st be as sho
w
n
on Page 9,
Figure 4
and may not be reversed. The air flo
w
m
u
st
be adj
u
sted s
u
ch that it is
w
ithin the acceptable
range sho
w
n on
Page 9, Section 6.1.3
. The
minim
u
m inlet d
u
ct lengths sho
w
n
on Page 9,
Section 6.1.1
sho
u
ld be observed. Press
u
re drop
thro
u
gh the heat exchanger at vario
u
s air flo
w
s is
given
on Page 9, Section 6.1.2
.
Fi
g
ure 4: Air Flow Direction
6.1.1 Minimum Inlet Duct Len
g
th
6.1.2 Temperature Rise and Pressure Drop Ran
g
es
6.1.3 Air Flow and Temperature Rise Ran
g
es
AIR FLO
W
OUTLET DUCT
I
N
LET DUCT
Model
Duct Len
g
th
Duct Size (W X H)
UHD[X][S] 75
32" (81 cm)
16 3/4" x 15 7/8" (43 cm x 40 cm)
UHD[X][S] 100 &125
37" (94 cm)
21 3/4" x 15 7/8" (55 cm x 40 cm)
UHD[X][S] 75
UHD[X][S] 100
UHD[X][S] 125
Airflow
(CFM)
Temperature
Rise (°F)
Pressure Drop
(in wc)
Airflow
(CFM)
Temperature
Rise (°F)
Pressure Drop
(in wc)
Airflow
(CFM)
Temperature
Rise (°F)
Pressure Drop
(in wc)
850
68
0.06
950
78
0.05
1,020
92
0.06
1,200
48
0.10
1,500
50
0.18
1,650
57
0.14
1,625
36
0.16
2,500
31
0.28
2,340
41
0.27
1,965
30
0.22
3,000
26
0.39
3,480
28
0.56
2,450
24
0.31
3,300
24
0.46
4,240
23
0.80
2,650
22
0.36
3,660
22
0.55
4,750
20
0.98
Model
Rate
Air Flow
Temperature Rise
(Btu/h)
Minimum (CFM)
Maximum (CFM)
Minimum (°F)
Maximum (°F)
UHD[X][S] 75
75,000
850
2,650
22
68
UHD[X][S] 100
100,000
950
3,660
22
78
UHD[X][S] 125
125,000
1,020
4,750
20
92
Summary of Contents for UHD 125
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 29: ...SECTION 9 GAS PIPING 21 of 47 Figure 14 Gas Connection...
Page 43: ...SECTION 14 TROUBLESHOOTING 35 of 47 14 1 General...
Page 54: ...UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL 46 of 47...
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......