9.6
mA OUTPUT SETTINGS FOR THE MEASUREMENT
Go to the menu OUTPUT mA FLOW
HIGHER 0360 m3
Enter the measured value for which the output is 20 mA, then confirm.
LOWER 0000 m3
Enter the measured value for which the output is 0 or 4 mA, then confirm.
OUTPUT 4/20 mA or 0/20 mA
Select the output signal type, then confirm.
SAVE ?
To record the settings, press the icon SAVE
9.7
mA OUTPUT SETTINGS FOR THE TEMPERATURE
Go to the menu OUTPUT mA TEMP.
160.0 °C
Enter the temperature value for which the output is 20 mA, then confirm.
LOWER +000.0 °C
Enter the temperature value for which the output is 0 or 4 mA, then confirm.
OUTPUT 4/20 mA or 0/20 mA
Select the output signal type, then confirm.
SAVE ?
To record the settings, press the icon SAVE
9.8
SIMULATION ON RELAYS
With the menu FORCED RELAY, it is possible to manually test (force) relays S1, S2, S3 and S4.
Last one, S4, is N.O. by default.
The test begins by relay S1.
The respective relay can be switched from OFF (open) to ON (closed).
Confirm to go to the next relay, then to go back to previous menu.
9.9
RESET THE DAILY VOLUME TO ZERO
Go to the menu RAZ Volume Jour = Rest daily volume to zero.
RESET D.V. YES / NO
Sélect YES to reset the counter to 0 on daily volume, then confirm, and SAVE.
DEB
21-12-2018
M-759.03-EN-AB
759-03
/11
Flow calculator
BAMOPHAR 759