9.2

THRESHOLD S1 AS ON/OFF MODE

ALARM 1 ON / OFF

To set in function the relay, select the ON mode, then confirm.
To disable the relay, select OFF mode, then confirm and save (Icon SAVE)

ALARM 1 MEASUREMENT / TEMP.

MEASUREMENT: Threshold dedicated to the flow rate measurement
TEMP.: Threshold dedicated to the temperature measurement
Select your mode, then confirm.

ALARM HIGH / LOW

HIGH: Triggering takes place as soon as measurement is greater than the threshold
LOW: Triggering takes place as soon as the measurement is lower than the threshold
Select the right triggering mode, then confirm

ON 1000 m³

Enter the value at which relay S1 will be actuated, then confirm.

OFF 0950 m³

Enter the value at which relay S1 will be deactivated, then confirm.

DELAY UP ON / OFF

With (ON) or without (OFF) pick-up delay for relay; then confirm.

TIME 0000 Sec

Enter a delay duration for relay S1, then confirm.

DELAY DOWN ON / OFF

With or without dropout delay for relay S1

TIME 0000 Sec

Enter a delay duration for relay; then confirm.

SAVE ?

To record the settings, press the icon SAVE

9.3

THRESHOLD S3 SET AS ON/OFF MODE AND ASSIGNMENT TO EXTERNAL SENSOR

Go to the menu ALARM 3

Setting sequences of S3 are identical to settings of S1 (see previous chapter)
THRESHOLD S3 has a second function: assignment to an external sensor (see further on)

ALARM 3 ON / OFF

Select the “ON” mode in order to activate the relay; Then confirm.

EXTERN NO / YES

NO: Setting will follow same sequences as per relays S1 in mode ON/OFF
YES = assignment of signal from external sensor to relay S3
The relay S3 becomes a N.C. contact; It will open when the function Regulation is in standby.

SAVE ?

To record the settings, press the icon SAVE

9.4

SETTING THE SAMPLER CONTROL (Relay S2)

Go to the menu SAMPLER CONTROL

SAMP. CONT. ON / OFF

To set the sampler control select ON ; then confirm.

ON 005.0 m³

Enter the value at which relay S2 will be actuated (sampling begins); then confirm.

PULSE SIGNAL

Confirm

TIME 0001 Sec

Enter the value at which relay S2 keeps actuated (pulse duration), then confirm and SAVE.

9.5

SETTING THE TEMPERATURE

Go to the menu TEMPERATURE

MEASURE : AUTO / MANUAL

AUTO : Temperature is displayed if a Pt 100 sensor is connected

MANUAL : Without Pt 100 sensor connected, enter the temperature manually.
Confirm

FLUID T. +025.0 °C

In the MANUAL mode, enter the temperature of the liquid, then confirm.

SAVE ?

To record the settings, press the icon SAVE

DEB

21-12-2018

M-759.03-EN-AB

759-03

/10

Flow calculator

BAMOPHAR 759

22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL

Tel

Fax

+33 (0)1 30 25 83 20

+33 (0)1 34 10 16 05

Web

E-mail

www.bamo.eu

[email protected]

INTERNATIONAL

Summary of Contents for BAMOPHAR 759

Page 1: ...MANUAL DEB 21 12 2018 M 759 03 EN AB 759 03 1 Flow calculator BAMOPHAR 759 22 Rue de la Voie des Bans Z I de la gare 95100 ARGENTEUIL Tel Fax 33 0 1 30 25 83 20 33 0 1 34 10 16 05 Web E mail www bamo...

Page 2: ...UREMENT PARAMETERS 9 2 10 THRESHOLD S1 AS ON OFF MODE 9 3 10 THRESHOLD S3 SET AS ON OFF MODE AND ASSIGNMENT TO EXTERNAL SENSOR 9 4 10 SETTING THE SAMPLER CONTROL Relay S2 9 5 10 SETTING THE TEMPERATUR...

Page 3: ...ay S3 Adjustable hysteresis from 0 to 100 Adjustable delay from 0 to 9999 s Sampler control S2 Programming in m on volume counter 1 contact N O potential free Adjustable timer from 0 to 9999 s Pulse o...

Page 4: ...ccess to slot by removing the cover Signal input 4 20 mA Signal input 4 20 mA DEB 21 12 2018 M 759 03 EN AB 759 03 4 Flow calculator BAMOPHAR 759 22 Rue de la Voie des Bans Z I de la gare 95100 ARGENT...

Page 5: ...l 19 S2 20 Threshold S1 N O contact Measurement of flow rate or temperature 21 S1 22 Threshold S3 N O contact Flow rate or temperature measurement 23 S3 Available for assignment to external sensor bec...

Page 6: ...ly Brown Brown Blue Black Brown Blue Black Output Inductive sensor 194 831 NPN N C Connection of a N C flow controller NPN code 194831 DEB 21 12 2018 M 759 03 EN AB 759 03 6 Flow calculator BAMOPHAR 7...

Page 7: ...symbol appears if relay is set up Designation of each measuring systems Measured values display Main unit flow and temperature Extension example with pH and temperature Monitor A is shown in yellow ma...

Page 8: ...ed CONSULTATION MODE Query mode RETURN KEY Return to previous screen CONFIRM Access to the next line of menu SAVE Save settings 7 DISPLAY SETTINGS Note To access to the display settings BAMOPHAR must...

Page 9: ...n we find the serial number The serial number SN is written on the identification label of the BAMOPHAR It appears as well in MENU icon i INFORMATION 9 SETTINGS 9 1 SETTING OF MEASUREMENT PARAMETERS C...

Page 10: ...e previous chapter THRESHOLD S3 has a second function assignment to an external sensor see further on ALARM 3 ON OFF Select the ON mode in order to activate the relay Then confirm EXTERN NO YES NO Set...

Page 11: ...0 mA or 0 20 mA Select the output signal type then confirm SAVE To record the settings press the icon SAVE 9 8 SIMULATION ON RELAYS With the menu FORCED RELAY it is possible to manually test force rel...

Reviews: