9.2
THRESHOLD S1 AS ON/OFF MODE
ALARM 1 ON / OFF
To set in function the relay, select the ON mode, then confirm.
To disable the relay, select OFF mode, then confirm and save (Icon SAVE)
ALARM 1 MEASUREMENT / TEMP.
MEASUREMENT: Threshold dedicated to the flow rate measurement
TEMP.: Threshold dedicated to the temperature measurement
Select your mode, then confirm.
ALARM HIGH / LOW
HIGH: Triggering takes place as soon as measurement is greater than the threshold
LOW: Triggering takes place as soon as the measurement is lower than the threshold
Select the right triggering mode, then confirm
ON 1000 m³
Enter the value at which relay S1 will be actuated, then confirm.
OFF 0950 m³
Enter the value at which relay S1 will be deactivated, then confirm.
DELAY UP ON / OFF
With (ON) or without (OFF) pick-up delay for relay; then confirm.
TIME 0000 Sec
Enter a delay duration for relay S1, then confirm.
DELAY DOWN ON / OFF
With or without dropout delay for relay S1
TIME 0000 Sec
Enter a delay duration for relay; then confirm.
SAVE ?
To record the settings, press the icon SAVE
9.3
THRESHOLD S3 SET AS ON/OFF MODE AND ASSIGNMENT TO EXTERNAL SENSOR
Go to the menu ALARM 3
Setting sequences of S3 are identical to settings of S1 (see previous chapter)
THRESHOLD S3 has a second function: assignment to an external sensor (see further on)
ALARM 3 ON / OFF
Select the “ON” mode in order to activate the relay; Then confirm.
EXTERN NO / YES
NO: Setting will follow same sequences as per relays S1 in mode ON/OFF
YES = assignment of signal from external sensor to relay S3
The relay S3 becomes a N.C. contact; It will open when the function Regulation is in standby.
SAVE ?
To record the settings, press the icon SAVE
9.4
SETTING THE SAMPLER CONTROL (Relay S2)
Go to the menu SAMPLER CONTROL
SAMP. CONT. ON / OFF
To set the sampler control select ON ; then confirm.
ON 005.0 m³
Enter the value at which relay S2 will be actuated (sampling begins); then confirm.
PULSE SIGNAL
Confirm
TIME 0001 Sec
Enter the value at which relay S2 keeps actuated (pulse duration), then confirm and SAVE.
9.5
SETTING THE TEMPERATURE
Go to the menu TEMPERATURE
MEASURE : AUTO / MANUAL
AUTO : Temperature is displayed if a Pt 100 sensor is connected
MANUAL : Without Pt 100 sensor connected, enter the temperature manually.
Confirm
FLUID T. +025.0 °C
In the MANUAL mode, enter the temperature of the liquid, then confirm.
SAVE ?
To record the settings, press the icon SAVE
DEB
21-12-2018
M-759.03-EN-AB
759-03
/10
Flow calculator
BAMOPHAR 759