STARTING UP AND REGULATION
•
Make sure that the mains voltage corresponds to the manufacturer's
requirements and that all electrical connections made at the
installation site are effected properly as illustrated in our wiring
diagram.
•
Make sure that the combustion products may be freely vented
through the boiler and flue dampers.
•
Check that there is water in the boiler and that the gate valves of the
system are open.
•
Check that all the gate valves fitted on the fuel suction and return
pipes are open; the same applies to any other fuel shut-off devices.
•
Bleed out the air contained in the gas piping, with due precautions
and with doors and windows open.
•
Open the union on the pipe near the burner and then open slightly
the gas shut-off cocks.
When the characteristic odour of gas can be smelled, close the cut-off
cock.
•
Wait the time necessary for the gas in the room to disperse outside.
Re-connect the burner to the gas pipeline.
•
Make sure that the combustion head is long enough to enter the
furnace following the measure specified by the boiler manufacturer.
•
Install a pressure gauge with adequate scale on the pressure outlet
of the gas pressure switch.
•
With the switch on the burner panel at the position “0” and the main
switch on, check, closing the contactor manually, that the motor
rotates in the right direction. If necessary, swap the two power cables
for the motor around to change the direction of rotation.
•
If using the inverter, see the specific instructions in the quick guide.
•
Turn the switch (S1) to “I” of the control panel to power the equipment
and close the thermostat line turning the selector (S24) to the "I"
position.
•
If thermostats or pressure switches (safety and boiler) are closed as
well, the operating cycle will start.
•
For the regulation of the burner, see “RAPID GUIDE TO
PROGRAMMING” and the specific instruction manual for the
electronic cam.
•
After setting the minimum load (200 digits), bring the burner up
to the maximum using the controls on the electronic cam keypad
and adjust all the points (from 200 digits to 999 digits) following the
regulation chart (see the electronic cam instructions in the attached
manual).
•
Check combustion (CO, O2, NOx) using the appropriate instrument
at all intermediate points on the modulation route (from 200 to 999),
checking the gas flow rate by reading the meter.
•
Check, with a suitable instrument, that the percentage of carbon
monoxide (CO) present in the fumes does not exceed the limit set
by regulations in force at the time of installation.
•
Now, check for the efficiency of automatic modulation operation by
switching the ETAMATIC apparatus to the “AUTOMATIC” position.
With this setting the modulation function will start only by using the
automatic control of the boiler probe.
•
Check the efficiency of the thermostats or boiler pressure switches
(they should shut down the burner when triggered).
0033010079
H1
H7
F 6.3A
S24
MV
FUSE
S1
H2
H1
OPERATION INDICATOR LIGHT
H2
LOCK-OUT WARNING LIGHT
H7
FAN MOTOR THERMAL SWITCH RELAY LOCK-OUT LAMP
MV
FAN MOTOR
S1
START/STOP SWITCH
S24
SWITCH ON/OFF
22 / 48
0006160489_202211
ENGLISH
Summary of Contents for TBG 320SLX ME
Page 2: ......
Page 37: ...SCHEMI ELETTRICI TBG 320 SLX ME 21 9A 35 48 0006160489_202211 ITALIANO...
Page 38: ...TBG 320 SLX ME 36 48 0006160489_202211 ITALIANO...
Page 39: ...TBG 320 SLX ME 37 48 0006160489_202211 ITALIANO...
Page 40: ...BA I1 I2 I3 I4 TBG 320 SLX ME 38 48 0006160489_202211 ITALIANO...
Page 41: ...TBG 320 SLX ME 39 48 0006160489_202211 ITALIANO...
Page 42: ...TBG 320 SLX ME 40 48 0006160489_202211 ITALIANO...
Page 43: ...TBG 480SLX ME 18460010 41 48 0006160489_202211 ITALIANO...
Page 44: ...TBG 480SLX ME 18460010 42 48 0006160489_202211 ITALIANO...
Page 45: ...TBG 480SLX ME 18460010 43 48 0006160489_202211 ITALIANO...
Page 46: ...TBG 480SLX ME 18460010 BA I1 I2 I3 I4 44 48 0006160489_202211 ITALIANO...
Page 47: ...TBG 480SLX ME 18460010 45 48 0006160489_202211 ITALIANO...
Page 48: ...TBG 480SLX ME 18460010 46 48 0006160489_202211 ITALIANO...
Page 50: ...48 48 0006160489_202211 ITALIANO...
Page 85: ...WIRING DIAGRAMS TBG 320 SLX ME 21 9A 35 48 0006160489_202211 ENGLISH...
Page 86: ...TBG 320 SLX ME 36 48 0006160489_202211 ENGLISH...
Page 87: ...TBG 320 SLX ME 37 48 0006160489_202211 ENGLISH...
Page 88: ...BA I1 I2 I3 I4 TBG 320 SLX ME 38 48 0006160489_202211 ENGLISH...
Page 89: ...TBG 320 SLX ME 39 48 0006160489_202211 ENGLISH...
Page 90: ...TBG 320 SLX ME 40 48 0006160489_202211 ENGLISH...
Page 91: ...TBG 480SLX ME 18460010 41 48 0006160489_202211 ENGLISH...
Page 92: ...TBG 480SLX ME 18460010 42 48 0006160489_202211 ENGLISH...
Page 93: ...TBG 480SLX ME 18460010 43 48 0006160489_202211 ENGLISH...
Page 94: ...TBG 480SLX ME 18460010 BA I1 I2 I3 I4 44 48 0006160489_202211 ENGLISH...
Page 95: ...TBG 480SLX ME 18460010 45 48 0006160489_202211 ENGLISH...
Page 96: ...TBG 480SLX ME 18460010 46 48 0006160489_202211 ENGLISH...
Page 98: ...48 48 0006160489_202211 ENGLISH...
Page 99: ......