ELECTRICAL CONNECTIONS
The three-phase or single-phase power supply line of the minimum suitable size for the power absorbed by the
burner must be provided with fuse switch. In addition, according to the Standards, a switch on the burner supply
line is required, arranged outside the boiler room in an easily reachable position.
All electrical lines must be protected with a flexible sheath, be firmly fixed and pass far from high-temperature
elements. See the diagrams for the electrical connections (line and thermostats).
DESCRIPTION OF THE OPERATION
In the burner, by closing the main circuit breaker if the thermostats are off, the control box is supplied. The fan motor
is thus enabled, and its operation determines the pre-ventilation of the combustion chamber. At the same time, the
combustion air damper control motor opens the air damper in the position corresponding to the maximum set.
The combustion chamber pre-ventilation step thus occurs with air damper in the high flame position. At the end
of the pre-ventilation step, the combustion air damper is restored to the low flame position. If the ventilation air
pressure control switch detects a sufficient pressure, the ignition transformer is started and the gas valves (main
and safety) are opened. The burner starts.
The quantity of gas (m
3
/h) supplied with the ignition flame can be regulated by operating on the air damper
control servomotor (see dr. n° 0002933651).
Note:
The ignition flame has a higher gas flow rate than the minimum modulation flow rate (see dr.
0002965).
The flame is thus present and, detected by its control device, it allows continuing and ending the ignition step by
disabling the ignition transformer and enabling the air damper control motor, which gradually sets the same to the
high flame position. The quantity of gas supplied with the high flame must be regulated by operating on the air
damper control servomotor (see dr. n° 0002933651). In case of absence of ignition flame, the control box stops
in “safety lock”.
In case of “safety lock” the valves are closed immediately.
To unlock the control box from the safety position, press the luminous button on the control box.
Note
: For the gas valve regulation, see the specific instructions in the following pages.
The air damper is actuated by a special electrical motor (see specific instructions in the following pages),
note that as the burner is shut down by the thermostat enable, the air damper is restored to the total closure
position by the control motor.
DESCRIPTION OF THE MODULATION OPERATION
When the burner is on at the minimum flow rate, if the modulation sensor allows it (adjusted to a higher pressure
or temperature value than that in the boiler), the air regulation servomotor start running, thus determining a gradual
increase of the combustion air supply, and consequently, of gas, until the maximum supply at which the burner is
regulated is reached. The air pressure increase in the ventilator is detected by the gas valve sensor, model MB-
VEF..., which gradually adjusts the gas supply to the also gradual air pressure variation.
The burner remains in the maximum supply position until the temperature or pressure reaches a sufficient valve to
determine the intervention of the modulation sensor, which makes the air regulation servomotor run in the reverse
direction with respect to the previous one.
The backward rotation and the air and gas supply reduction occur at short time intervals.
With this operation, the modulation system attempts to balance the quantity of heat supplied to the boiler with
that yielded by the same during use.
The modulation probe applied to the boiler detects the request variations and automatically provides to adjusting
the fuel and the combustion air supply by enabling the air regulation servomotor with increasing or decreasing
rotation. If the limit value (temperature or pressure) is reached also with minimum supply to which the total shut
down device is set (thermostat or pressure switch), the burner is shut down by the intervention of the same. As
the temperature or pressure fall below the shut down device enable value, the burner is started again according
to the previously described program.
If the flame does not appear, the control box “locks” (total burner shut down and lighting of the relevant warning
light). To “unlock” the control box, press the special push button.
Summary of Contents for SPARKGAS 30 LX
Page 2: ......
Page 27: ...25 76 0006080799_200708 ...
Page 28: ...26 76 0006080799_200708 ...
Page 39: ...37 76 0006080799_200708 LMG 2 CONTROL BOX SPECIFICATIONS ...
Page 40: ...38 76 0006080799_200708 LMG 2 CONTROL BOX SPECIFICATIONS ...
Page 51: ...49 76 0006080799_200708 ...
Page 52: ...50 76 0006080799_200708 ...
Page 53: ...51 76 0006080799_200708 ...
Page 65: ...63 76 0006080799_200708 ...
Page 66: ...64 76 0006080799_200708 ...
Page 69: ...67 76 0006080799_200708 ...
Page 76: ...74 76 0006080799_200708 ...
Page 77: ...75 76 0006080799_200708 ...
Page 78: ...76 76 0006080799_200708 ...
Page 79: ......