N° 8666/3
12 / 44
0006080103_201309
HYDRAULIC DRAWING OF SUPPLY LINE TO LIQUID FUEL TWO-STAGE
BURNERS WITH MAXIMUM NOMINAL VISCOSITY (5°E AT 50°C)
ENGLISH
The diesel fuel recovery tanks (diameter ~ 150, height ~ 400)
should be installed as near as possible to the burner and should
be about 0,5 m. higher with respect to the burner’s pump.
1 - Main tank
2 - Filter
3 - Circulation pump
4 - Water and system outlet
5 -Air/gas outlet - normally closed
6 - Fuel and degasser recovery
7 - Non-return valve
8 - By-pass (normally closed)