6 / 18
0006081092_201305
ENGLISH
ETAMATIC CURVE ADJUSTMENT TABLE
BURNER: ………………..
s/n…………………… BOILER: ………………...…..………………………………………................
POINT ETAMATIC
LOAD
VALUE
(digit)
CH 1 INVERTER
SET POINT
(digit)
CH 3
GAS SET
POINT
(digit)
CH 4
AIR
SET
POINT
(digit)
ENGINE
FREQ.
(Hz)
I
(mA)
(*)
GAS FLOW
(m
3
/ h)
AIR
PRESS.
(mbar)
CO (ppm)
O2 %
CO2 % OVERHEAD
GAS
PRESS.
(mbar)
GAS
THROTTLE
ANGLE
WITHOUT
CURR.
CO
WITH
CURR.
CO
WITHOUT
CURR.
CO
WITH
CURR.
CO
WITHOUT
CURR.
CO
WITH
CURR.
CO
P0 (ignition)
ZP (2)
P1 (min)
200
P2
300
P3
400
P4
500
P5
600
P6
700
P7
800
P8
900
P9 (max)
990
USER
……………………...…...……………………………………………………………………………………………………………………………………………..
NOTES:
…………………………………………………………………………………………………………………………………………………………………………..
........................................................................................................................................................................................................................................
PAR N°
DIGIT
eTamaTiC ParameTers
(*) = Try to have the same flow difference between one pint and another (P9 - P1):8
Potentiometer digit adjustment:
Gas servomotor: min…….. ; max:…….
Air servomotor: min…….. ; max:…….
PAR N°
DIGIT
PAR N°
DIGIT
PAR N°
DIGIT
During operation with light oil maintain a
good excess of air in the chimney O2 = 5/6%.
Check the level of smoke with the minimum and maximum
thermal output of the burner using a "BACHARA pump” to
avoid O2 probe damage.
PiD ParameTer TabLe
Type of adjustment
P=805 P (%)
P=806 I (sec)
P=807 D(sec)
Very slow
30
400
10
Slow
15
320
40
Normal
7
90
50
Fast
4
35
17
Very fast
40
55
15
During operation with light oil, the CO probe cuts out, and
the burner works with the O2 curve.