ENGLISH
13 / 28
0006080871_201711
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
1
Fuel tank.
3
Wire-net filter.
4
Burner.
6
Suction pipe.
7
Burner return pipe.
8
Automatic fuel shut-off device with burner off.
9
Non-return valve.
10 Foot valve.
Height "P" maximum 3.5m
H metres
Total L. metres Øi 10mm
1
30
2
35
3
40
4
45
INTAKE SUPPLY SYSTEM
1
Fuel tank.
3
Wire-net filter.
4
Burner.
6
Suction pipe.
7
Burner return pipe.
10 Foot valve.
H Difference in level between minimum fuel level in the tank and pump
axis
L Total length of each pipeline, including vertical length.
i Inner pipe diameter
H metres
Total L. metres
Øi 10mm
Øi 12mm
0,5
26
54
1
24
47
1,5
18
38
2
14
30
2,5
10
23
3
6
15
3,5
-
7