SQN 30.111 A3500
PREVENTILATION WITH AIR OPEN (2
nd
FLAME POSITION) AIR CLOSED WITH BURNER IN STOP POSITION
In order to modify the cams regulation it's necessary to
intervene on the relative red rings. Pushing by sufficient
strength,in the sens one desires, each red ring can
turn in respect to the reffering scale. The pointer of the
red ring indicates on the respective reffering scale the
rotation angle set for each cam.
1
-
2nd Flame valve connection cam (must be adjusted in a position between the 1st flame and the 2nd flame cam)
2
-
Air regulation cam 1° flame
3
-
Close air shutter cam with burner in stop position
4
-
Air regulation cam 2
nd
flame
2
3
4
1
Motor-cam shaft coupling cutting out pin.
The switching-off of the motor and shaft connection can be
obtained by pushing.