INSTRUCTIONS LFL 1.... CONTROL BOX
N°
7
451
Rev. 10/1997
EN
Control box for burners of average and high power, with forced draught, intermittent service (*), 1 or 2 stages, or
modulating types, with supervision of the air pressure for controlling the air damper.
This control box bears the EC mark, in accordance with the Gas and Electromagnetic Compatibility Directive.
* For reasons of safety, it is necessary to make at least one controlled stop every 24 hours!
As regards the standards
The following LFL1… features exceed the standards, offering a high level of additional safety:
- The flame detector test and false flame test start immediately after the tolerated post-combustion time. If the valves remain
open, or do not close completely after adjustment stops, a lock-out stop is triggered at the end of the tolerated post-combustion
period. The tests will end only at the end of the pre-ventilation time of the next start-up.
- The validity of working of the flame control circuit is checked each time the burner starts up.
- The fuel valve control contacts are checked for wear during the post-ventilation time.
- A built-in fuse in the appliance protects the control contacts from any overloads that may occur.
As regards the burner control
- The equipment allows operation with or without post-ventilation.
- Controlled activation of the air damper to ensure pre-ventilation with nominal airflows. Positions checked: CLOSED or MIN
(position of ignition flame on start-up); OPEN at the beginning and MIN at the end of the pre-ventilation time. If the servomotor
does not position the air damper at the points described, the burner does not start-up.
- Ionization current minimum value = 6mA
- UV cell current minimum value = 70mA
- Phase and neutral must not be inverted.
- Any place may be used for installation and assembly (IP40 protection).
BGN 540 LX / LX-V ELECTRODES ADJUSTMENT DIAGRAM
N° 0002933850
Rev. 12/06/2002
1 -
Ionisation electrode
2 -
Ignition electrode
3 -
Flame disk
4 -
Gas diffuser
5 -
Gas delivery pipe
BGN 60 ÷ 390 LX / LX-V
ELECTRODES ADJUSTMENT DIAGRAM
N° 0002934430
Rev. 23/09/2004
MOD.
A
B
BGN 60 LX/LX-V
5
5
BGN 120 LX/LX-V
5
5
BGN 200 LX/LX-V
5
5
BGN 300 LX/LX-V
5
5
BGN 390 LX/LX-V
5
5
Summary of Contents for BGN 40 LX-V
Page 95: ...95 Coffrets de s curit pour br leurs gaz LFL 1 08 10 1997...
Page 96: ...96 Coffrets de s curit pour br leurs gaz LFL 1 08 10 1997...
Page 97: ...97 Coffrets de s curit pour br leurs gaz LFL 1 08 10 1997...
Page 98: ...98 Coffrets de s curit pour br leurs gaz LFL 1 08 10 1997...
Page 99: ...99 Coffrets de s curit pour br leurs gaz LFL 1 08 10 1997...
Page 108: ...108 DUNGS mod DMV VEF 5065 11 5125 11 N 0006080717 n 2 di 7 Rev 2002 06...
Page 109: ...109 DUNGS mod DMV VEF 5065 11 5125 11 N 0006080717 n 3 di 7 Rev 2002 06...
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......