Analyse combustion gases and check that the emission values are
correct at least once a year, in compliance with current law.
Carry out the following operations at the end of the heating season:
•
Clean air dampers, the air pressure switch with pressure port and
the relevant pipe (if fitted).
•
Check the electrode condition. Replace them, if necessary.
•
Have the burner and the chimney cleaned by specialised personnel
(stove repairer); a clean burner is more efficient, lasts longer and
is quieter.
•
In order to clean the combustion head, its outlet and components
must be disassembled. Be careful during the reassembly operations
to exactly centre the gas diffuser with respect to the electrodes,
making sure that they are not earthed, which would result in the
locking of the burner. Verify also that the ignition electrode spark
takes place exclusively between itself and the perforated sheet
metal disk (see combustion head and electrode disk distance
regulation diagram) for the version without pilot.
•
Analyse combustion gases and check emissions values.
•
Check that all components of the combustion head are in good
condition, have not been deformed and are free from deposits
deriving from the installation environment and/or from poor
combustion.
If it is necessary to clean the combustion head, remove its components
according to the procedure described below:
•
unscrew the anchoring screws -12 and open the ventilating body;
•
Pull out the ignition and ionisation cables -14 from their electrode
terminals -13;
•
Unscrew the screw -16 on the buffer -17;
•
pull out the entire mixer unit in the direction shown by the arrow.
•
When you have finished maintenance work, proceed to reassemble
the combustion head, following the same procedure in reverse,
after checking the correct position of the ignition electrodes.
12
12
14
14
13
13
16
17
Summary of Contents for 67200010
Page 2: ......
Page 25: ...ITALIANO 23 28 0006081514_201711 SCHEMI ELETTRICI TBG 480 2000 ME ...
Page 26: ...ITALIANO 24 28 0006081514_201711 TBG 480 2000 ME ...
Page 27: ...ITALIANO 25 28 0006081514_201711 TBG 480 2000 ME ...
Page 28: ...ITALIANO 26 28 0006081514_201711 TBG 480 2000 ME ...
Page 30: ......
Page 53: ...ENGLISH 23 28 0006081514_201711 WIRING DIAGRAMS TBG 480 2000 ME ...
Page 54: ...ENGLISH 24 28 0006081514_201711 TBG 480 2000 ME ...
Page 55: ...ENGLISH 25 28 0006081514_201711 TBG 480 2000 ME ...
Page 56: ...ENGLISH 26 28 0006081514_201711 TBG 480 2000 ME ...
Page 58: ......
Page 59: ......