BIW1-A/C/E/G310-M_ _ _ _-P1-S115
Micropulse Linear Transducer in Profile Housing

english

6

5

Startup

5.1

Check connections

Although the connections are polar-
ity reversal protected, components
can be damaged by improper con-
nections and overvoltage. Before
you apply power, check the connec-
tions carefully.

5.2

Turning on the system

Note that the system may execute
uncontrolled movements when first
turned on or when the transducer is
part of a closed-loop system whose
parameters have not yet been set.
Therefore make sure that no haz-
ards could result from these
situations.

5.3

Check output values

After replacing or repairing a trans-
ducer, it is advisable to verify the
values for the start and end position
of the sliding rod in manual mode.

5.4

Check functionality

The functionality of the transducer
system and all its associated com-
ponents should be regularly
checked and recorded.

5.5

Fault conditions

When there is evidence that the
transducer system is not operating
properly, it should be taken out of
service and guarded against unau-
thorized use.

Supply voltage

3 = DC 24 V potential isolated

Electr. connection: with connector S115

BIW1-A310-M0450-P1-S115

Profile form factor

Nom. length (4digits): M = metric in mm

Interface: A = 0...+10 V

C = 0...20 mA
E = 4...20 mA
G =  -10...+10 V

Micropulse

Linear T

ransducer

6

Versions (indicated on part label)

Ordering
code:

 

BIW_ _ _ _

Type:

6.1

Included in shipment

Transducer with condensed guide
and 2 mounting brackets.

6.2

Available lengths

The following nominal stroke
lengths are available:

0075, 0100, 0130, 0150, 0175,
0225, 260, 0300, 0360, 0375,
0400, 0450, 0500, 0600, 0650,
0750

Other stroke lengths on request.

6.3

Accessories 

(optional)

Connectors

    ➥

 Fig. 4-3

straight:

BKS-S115-PU-_ _

right angle:

BKS-S116-PU-_ _

Summary of Contents for BIW1-A310-M -P1-S115 Series

Page 1: ...310 M_ _ _ _ P1 S115 Betriebsanleitung deutsch Balluff GmbH Schurwaldstra e 9 73765 Neuhausen a d F Deutschland Tel 49 7158 173 0 Fax 49 7158 5010 Service Center 49 7158 173 370 service balluff de www...

Page 2: ...andere Technische Daten gelten z B bei Abgleich An schluss oder Abmessungen Inhaltsverzeichnis 1 Sicherheitshinweise 2 1 1 Bestimmungsgem e Verwendung 2 1 2 Qualifiziertes Personal 2 1 3 Einsatz und...

Page 3: ...srichten 2 Befestigungsschrauben mit max 2 Nm anziehen Geh usel nge A Nennl nge 100 mm mechanischer Nullpunkt B0 0 2 mm elektrischer Nullpunkt B0 5 mm elektrischer Hub mechanischer Hub B Nennl nge 10...

Page 4: ...BIW1 A310 S115 YE GY PK RD GN BU BN WH Steigungsauswahl 0 V reserviert Steigungsauswahl 0 10 V GND 24 V DC reserviert Steuerung 1 2 3 4 5 6 7 8 Bild 4 1 BIW1 A310 M S115 mit Steuerung und BKS S115 PU...

Page 5: ...on Phasenanschnittsteue rungen f r die der Kabelschirm nur geringen Schutz bietet L nge des Kabels max A G 25 m C E 100 m 6 bis 8 mm L ngere Kabel sind einsetzbar wenn durch Aufbau Schirmung und Verle...

Page 6: ...t sind Stellen Sie daher sicher dass hiervon keine Gefahren ausgehen k nnen 5 3 Messwerte pr fen Nach dem Austausch bzw nach der Reparatur eines Wegauf nehmers wird empfohlen die Wer te in der Anfangs...

Page 7: ...ll nge A G 25 m C E 100 m Nr 837 922 726 D 03 111450 Ausgabe 1004 nderungen vorbehalten Ersetzt Ausgabe 0908 In Verbindung mit diesem Produkt wurden folgende Patente erteilt US 2003 0206007 A1 DE 102...

Page 8: ...E G310 M_ _ _ _ P1 S115 Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germany Phone 49 7158 173 0 Fax 49 7158 5010 Service Center 49 7158 173 370 service balluff de www balluff com User s Guid...

Page 9: ...n in the part number other technical data may apply affect ing calibration wiring dimensions etc Contents 1 Safety Advisory 2 1 1 Proper application 2 1 2 Qualified personnel 2 1 3 Use and inspection...

Page 10: ...ng screws to a maximum of 2 Nm Housing length A Nominal length 100 mm Mechanical zero point B0 0 2 mm Electrical zero point B0 5 mm Electrical stroke mechanical stroke B Nominal length 10 mm Clamp spa...

Page 11: ...BU BN WH Output slope 0 V Reserved Output slope 0 10 V GND 24 V DC Reserved Controller 1 2 3 4 5 6 7 8 Fig 4 1 BIW1 A310 M S115 with controller and BKS S115 PU05 Connection example Table 4 1 Wiring as...

Page 12: ...caused by AC harmonics e g from phase control devices against which the cable shield provides only limited protection Cable length max A G 25 m C E 100 m 6 to 8 mm Longer lengths may be used if constr...

Page 13: ...nality The functionality of the transducer system and all its associated com ponents should be regularly checked and recorded 5 5 Fault conditions When there is evidence that the transducer system is...

Page 14: ...uit protection built in Cable length A G 25 m C E 100 m No 837 922 726 E 03 111450 Edition 1004 specifications subject to changes Replaces edition 0908 The following patents have been granted in conne...

Page 15: ..._ _ _ P1 S115 Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F R F A T l phone 49 7158 173 0 T l copieur 49 7158 5010 Service Center 49 7158 173 370 service balluff de www balluff com Notice d ut...

Page 16: ...panneau signal tique existent avec d autres caract ristiques techniques par ex pour le r glage le branchement ou les dimensions Sommaire 1 Consignes de s curit 2 1 1 Utilisation prescrite 2 1 2 Perso...

Page 17: ...barre coulissante 2 Serrez les vis de fixation avec un couple d au plus 2 Nm Longueur du bo ter A Longueur nom 100 mm Origine m canique B0 0 2 mm Origine lectrique B0 5 mm Lev e lectrique lev e m can...

Page 18: ...BN WH choix de la pente 0 V r serv e choix de la pente 0 10 V GND 24 V DC r serv e Commande 1 2 3 4 5 6 7 8 Fig 4 1 BIW1 A310 M S115 et commande et BKS S115 PU05 exemple de raccordement Tableau 4 1 A...

Page 19: ...stes p ex provenant des automates d cou page de phase car le blindage des c bles n en assure que faiblement la protection Longueur max des c bles A G 25 m C E 100 m 6 8 mm Il est possible de pr voir d...

Page 20: ...itiale et finale 5 4 Contr le de la capabilit de fonctionnement La capabilit de fonctionnement du syst me de mesure de d place ment et celle de tous les compo sants y aff rents doit tre v rifi e r gul...

Page 21: ...ures typique 32 kHz 30 33 kHz Protection de court circuit incorpor e Longueur du c ble A G 25 m C E 100 m N 837 922 726 F 03 111450 Edition 1004 sous r serve de modifications Remplace l dition 0908 Le...

Page 22: ...0 M_ _ _ _ P1 S115 Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Alemania Tel 49 7158 173 0 Fax 49 7158 5010 Service Center 49 7158 173 370 service balluff de www balluff com Manual de instruc...

Page 23: ..._ en la placa de caracter sticas pueden aplicarse otras Caracter sticas T cnicas p ej en el caso de compensaci n conexi n o dimensiones Indice 1 Indicaciones de seguridad 2 1 1 Uso debido 2 1 2 Person...

Page 24: ...esplazamiento con con barra de empuje 2 Apretar los tornillos de fijaci n a un m x de 2 Nm Longitud de la caja A Longitud nom 100 mm Punto cero mec nico B0 0 2 mm Punto cero el ctrico B0 5 mm Carrera...

Page 25: ...n elegida BIW1 A310 S115 YE GY PK RD GN BU BN WH selecci n de ascenso 0 V reservado selecci n de ascenso 0 10 V GND 24 V DC reservado PLC 1 2 3 4 5 6 7 8 Fig 4 1 BIW1 A310 M S115 con PLC y BKS S115 PU...

Page 26: ...inyectadas por los arm nicos de la red p ej debido al efecto de controles de ngulo de fase para las cuales la pantalla del cable ofrece una protecci n tan solo reducida Longitud m x del cable A G 25...

Page 27: ...do manual 5 4 Comprobar la funcionalidad La funcionalidad del sistema de medici n de desplazamiento lineal y de todos los componentes aso ciados a ste debe verificarse pe ri dicamente y reflejarse en...

Page 28: ...orporada Longitud del cable A G 25 m C E 100 m N 837 922 726 SP 03 111450 Edici n 1004 Reservado el derecho a introducir modificaciones Sustituye a edici n 0908 En relaci n con este producto se han co...

Page 29: ...310 M_ _ _ _ P1 S115 Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germania Telefono 49 7158 173 0 Fax 49 7158 5010 Service Center 49 7158 173 370 service balluff de www balluff com Manuale d...

Page 30: ..._ _ _ sulla targhetta tipo possono valere dati tecnici diversi ad es per la compensazione l attacco o le dimensioni Indice 1 Indicazioni per la sicurezza 2 1 1 Uso proprio 2 1 2 Personale qualificato...

Page 31: ...osizione con la biella 2 Serrare le viti di fissaggio con max 2 Nm Lunghezza dell involucro A Lungh nom 100 mm Punto zero meccanico B0 0 2 mm Punto zero elettrico B0 5 mm Corsa elettrica corsa meccani...

Page 32: ...1 A310 S115 YE GY PK RD GN BU BN WH Selezione del gradiente 0 V riservato Selezione del gradiente 0 10 V GND 24 V DC riservato Unit di comande 1 2 3 4 5 6 7 8 Fig 4 1 BIW1 A310 M S115 con unit di coma...

Page 33: ...uttive dovute ad armoniche di rete per es comandi a ritardo di fase alle quali la schermatura del cavo offre una protezione ridotta Lunghezza del cavo A G 25 m C E 100 m da 6 a 8 mm Possono essere uti...

Page 34: ...nale della biella 5 4 Controllo funzionamento Il funzionamento del trasduttore di posizione e di tutte le componenti ad esso connesse deve essere pe riodicamente verificato e protocollato 5 5 Difetti...

Page 35: ...one contro i corti circuiti incorporata Lunghezza del cavo A G 25 m C E 100 m N 837 922 726 I 03 111450 Edizione 1004 Ci si riserva il diritto di modifiche Sostituisce l edizione 0908 In relazione a q...

Reviews: