BIS V-6106 Ethernet/IP™
Processor Unit
22
Note
To achieve the read times specified
on page 63
in dynamic operation, the
Tag Type
parameter has to be set to "BIS C 32 Byte" or "BIS C 64 Byte" on the respective
head.
For read/write heads BIS VU:
Balluff data carrier type
Manufacturer
Memory capacity
BIS U-1_ _
Balluff
See Data Sheet
Note
The read/write head BIS VU generally supports data carriers regardless of
manufacturer, that meet the standards set by EPCglobal™ Class 1 Generation 2 or
ISO IEC 18000-63.
The IO-Link port of the BIS V-6106 can be operated as a digital standard I/O or as an IO-Link
port.
Configuration options:
– 0: Standard I/O
– 1: IO-Link functionality
The cycle time controls the timing for triggering the IO-Link device. The factory default setting is
0 (Auto). It is recommended that this value be retained.
The cycle time is stored in the IO-Link device (slave) and is detected automatically. Only times
that are slower than the automatically selected times can be set manually.
Whether a connected IO-Link device receives access to the IO-Link master can be controlled
using validation.
Configuration options:
– 0
No validation
– 1
Compatible
Only allows communication to the IO-Link master for devices whose vendor ID (VID) and
device ID (DID) correspond to the configured values.
– 2
Identical
See "1 Compatible"; in addition, the serial number of the IO-Link device is checked
Vendor ID for the IO-Link device (refer to the manual for the device)
Device ID for the IO-Link device (refer to the manual for the device)
Serial number for the IO-Link device (if available; refer to the IO-Link device's type plate)
Tag type
IO-Link port
function
Cycle time
Validation type
IOL Vendor ID
(VID)
IOL Device ID
(DID)
IOL Serial
number, optional
6
Startup