BIS V-6106 Ethernet/IP™
Processor Unit
23
Automatic upload (IO-Link slave
ĺ
IO-Link master) or download (IO-Link master
ĺ
IO-Link
slave) can be switched on using this parameter.
For automatic upload, the parameter configuration is read when an IO-Link device is plugged in.
For automatic download, the parameter configuration is transmitted to the device when an
IO-Link device is plugged in.
Background:
The automatic upload makes it possible to read in the parameter configuration of a
correctly
configured device when plugging one in. If an IO-Link device has to be replaced, the previously
read in parameter configuration from the
old
device is transferred to the
new
device when it is
plugged in.
The "Upload" option can be disabled by having a valid parameter set read.
Configuration options:
– 8X
hex
: Switch on
– X1
hex
: Switch on upload
– X2
hex
: Switch on download
Parameter server,
optional
6
Startup