www.balluff.com
109
english
Value
Meaning
0xA07E (41086) PD Pre-Alarm a-RMS Z
0xA07F (41087)
PD Pre-Alarm a-RMS M
0xA080 (41088)
PD Main-Alarm a-RMS X
0xA081 (41089)
PD Main-Alarm a-RMS Y
0xA082 (41090)
PD Main-Alarm a-RMS Z
0xA083 (41091)
PD Main-Alarm a-RMS M
0xA084 (41092)
PD Pre-Alarm a-Peak X
0xA085 (41093)
PD Pre-Alarm a-Peak Y
0xA086 (41094)
PD Pre-Alarm a-Peak Z
0xA087 (41095)
PD Pre-Alarm a-Peak M
0xA088 (41096)
PD Main-Alarm a-Peak X
0xA089 (41097)
PD Main-Alarm a-Peak Y
0xA08A (41098) PD Main-Alarm a-Peak Z
0xA08B (41099) PD Main-Alarm a-Peak M
Tab. 6-3: Switching Counter – Switching Counter Input
Switching Counter Mode
With
Switching Counter Mode
, the current mode of the
counter function can be selected.
Value
Meaning
Description
0x00 (0) Deactivated
Deactivated
0x01 (1) Static
Static counter function
0x02 (2) Auto
Auto counter function
Tab. 6-4: Switching Counter – Switching Counter Mode
Switching Counter Limit
With
Switching Counter Limit
, the count limit for the
counter can be set. The value range is between 0x0002 (2)
and 0xFFFF (65535).
Switching Counter Detection Type
With
Switching Counter Detection Type
the current type of
counting can be selected.
Value
Meaning
Description
0x00 (0) Rising Edge Counter is incremented with
rising edge (from 0/false to 1/
true).
0x01 (1) Falling Edge Counter is incremented with
falling edge (from 1/true to 0/
false).
0x02 (2) Both Edges
Counter is incremented for
each edge.
Tab. 6-5: Switching Counter – Switching Counter Detection Type
6
Secondary device functions (continued)
Switching Counter Startup Delay
With
Switching Counter Startup Delay
, the time for the
startup delay can be set. The startup delay begins after the
supply voltage is switched on. During the startup delay,
the counter has no function. The counter starts after the
startup delay has elapsed. The value represents the time in
seconds. The value range is between 0x00 (0) and 0xFF
(255). A value of 0x00 (0) represents no start delay.
Switching Counter State
With
Switching Counter State
, the current status can be
read.
Value
Meaning
Description
0x00 (0) Not reached
Value
is less than
Limit
.
0x01 (1) reached
Value
is greater than or equal to
Limit
.
0x03 (3) exceeded
Value
is greater than
Limit
.
0x08 (8) Startup
Delay
Startup delay currently running.
0xFF
(255)
Deactivated
Feature is deactivated.
Tab. 6-6: Switching Counter – Switching Counter State
Switching Counter Value
With
Switching Counter Value
, the current counter value
can be read.
Switching Counter Reset
With
Switching Counter Reset
individual or all channels
can be reset by resetting the counter value and the flags.
Value
Meaning
Description
0x01 (1) Channel 1
Reset
Channel 1 is reset.
0x02 (2) Channel 2
Reset
Channel 2 is reset.
0x03 (3) Channel 3
Reset
Channel 3 is reset.
0x04 (4) Channel 4
Reset
Channel 4 is reset.
0xFF
(255)
Channel All
Reset
All channels are reset.
Tab. 6-7: Switching Counter – Switching Counter Reset
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor