38
english
3
Overview of IO-Link data and functions (continued)
Name
Index
Sub-
index
Access
Length
Data Type
Data
Storage
Default
Pin 2 Configuration
Pin 2 Function
Configuration
0x2195
(8597)
0
RW
1 byte
UINT8
Yes
0
RPM Input
1)
RPM Configuration
0x2196
(8598)
0
RW
4 bytes
Array
n/a
–
RPM Input Source
1
RW
1 byte
UINT8
n/a
0
(Min.: 0 / Max.: 2)
RPM Static
2
RW
2 bytes
UINT16
n/a
0
(Min.: 0 / Max.: 65535)
RPM Divider
3
RW
1 byte
UINT8
n/a
1
(Min.: 1 / Max.: 255)
RPM Used
0x2197
(8599)
0
RO
2 bytes
UINT16
n/a
–
Custom Alarm
Custom Alarm Input
0x2193
(8595)
0
RW
4 bytes
UINT16[]
n/a
–
Custom Alarm Input 1
1
RW
2 bytes
UINT16
n/a
0
Custom Alarm Input 2
2
RW
2 bytes
UINT16
n/a
0
Device Status and Detailed Device Status
Device Status
0x0024
(36)
0
R
1 byte
UINT8
n/a
n/a
Detailed Device Status
0x0025
(37)
0
R
30 bytes
UINT8[]
n/a
n/a
Diagnosis Suppression
Diagnosis Level
Configuration
0x0070
(112)
0
R/W
1 byte
UINT8(ENUM)
Yes
0
Event Code
Suppression
0x0071
(113)
0
R/W
10 bytes
–
Yes
–
Event Code
Suppression
1…5
R/W
2 bytes
UINT16
No
0
Event Code
Suppression Teach-in
0x0072
(114)
0
W
2 bytes
UINT16
n/a
–
Event Code
Suppression Delete
0x0073
(115)
0
W
2 bytes
UINT16
n/a
–
Reset Commands
System Commands
0x0002
(2)
0
W
1 byte
UINT8
n/a
–
1)
only for BCM R16E-004-CI02-_ _ , _-S4
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor