www.balluff.com
49
english
5
Primary device functions (continued)
Object
ID
Name
Description
Direction
0xA042
PD Main-Alarm
a-RMS
Cumulative flag of PD Main-Alarm a-RMS X, PD Main-Alarm a-RMS Y, PD Main-
Alarm a-RMS Z, PD Main-Alarm a-RMS M
based on the values of
Enable Alarms a-RMS X
,
Enable Alarms a-RMS Y
,
Enable
Alarms a-RMS Z, Enable Alarms a-RMS M
.
1 – If
(PD Main-Alarm a-RMS X AND Enable Alarm a-RMS X is set) OR
(PD Main-Alarm a-RMS Y AND Enable Alarm a-RMS Y is set) OR
(PD Main-Alarm a-RMS Z AND Enable Alarm a-RMS Z is set) OR
(PD Main-Alarm a-RMS M AND Enable Alarm a-RMS M is set)
0 – If
(PD Main-Alarm a-RMS X OR Enable Alarm a-RMS X is cleared) AND
(PD Main-Alarm a-RMS Y OR Enable Alarm a-RMS Y is cleared) AND
(PD Main-Alarm a-RMS Z OR Enable Alarm a-RMS Z is cleared) AND
(PD Main-Alarm a-RMS M OR Enable Alarm a-RMS M is cleared)
Input
0xA045
PD Pre-Alarm
a-Peak
Cumulative flag of PD Pre-Alarm a-Peak X, PD Pre-Alarm a-Peak Y, PD Pre-
Alarm a-Peak Z, PD Pre-Alarm a-Peak M
based on the values of
Enable Alarms a-Peak X
,
Enable Alarms a-Peak Y
,
Enable
Alarms a-Peak Z, Enable Alarms a-Peak M
.
1 – If
(PD Pre-Alarm a-Peak X AND Enable Alarm a-Peak X is set) OR
(PD Pre-Alarm a-Peak Y AND Enable Alarm a-Peak Y is set) OR
(PD Pre-Alarm a-Peak Z AND Enable Alarm a-Peak Z is set) OR
(PD Pre-Alarm a-Peak M AND Enable Alarm a-Peak M is set)
0 – If
(PD Pre-Alarm a-Peak X OR Enable Alarm a-Peak X is cleared) AND
(PD Pre-Alarm a-Peak Y OR Enable Alarm a-Peak Y is cleared) AND
(PD Pre-Alarm a-Peak Z OR Enable Alarm a-Peak Z is cleared) AND
(PD Pre-Alarm a-Peak M OR Enable Alarm a-Peak M is cleared)
Input
0xA046
PD Main-Alarm
a-Peak
Cumulative flag of PD Main-Alarm a-Peak X, PD Main-Alarm a-Peak Y, PD Main-
Alarm a-Peak Z, PD Main-Alarm a-Peak M
based on the values of
Enable Alarms a-Peak X
,
Enable Alarms a-Peak Y
,
Enable
Alarms a-Peak Z, Enable Alarms a-Peak M
.
1 – If
(PD Main-Alarm a-Peak X AND Enable Alarm a-Peak X is set) OR
(PD Main-Alarm a-Peak Y AND Enable Alarm a-Peak Y is set) OR
(PD Main-Alarm a-Peak Z AND Enable Alarm a-Peak Z is set) OR
(PD Main-Alarm a-Peak M AND Enable Alarm a-Peak M is set)
0 – If
(PD Main-Alarm a-Peak X OR Enable Alarm a-Peak X is cleared) AND
(PD Main-Alarm a-Peak Y OR Enable Alarm a-Peak Y is cleared) AND
(PD Main-Alarm a-Peak Z OR Enable Alarm a-Peak Z is cleared) AND
(PD Main-Alarm a-Peak M OR Enable Alarm a-Peak M is cleared)
Input
0xA047
Severity Zone
A
1 – If the largest value of PD v-RMS X, PD v-RMS Y, PD v-RMS Z, PD v-RMS M
doesn't exceed Severity Zone Boundary A/B for at least Alarm Set Delay ms.
0 – If the largest value of PD v-RMS X, PD v-RMS Y, PD v-RMS Z, PD v-RMS M
exceeds Severity Zone Boundary A/B for at least Alarm Set Delay ms.
Input
0xA048
Severity Zone
B
1 – If the largest value of PD v-RMS X, PD v-RMS Y, PD v-RMS Z, PD v-RMS M is
between Severity Zone Boundary A/B and Severity Zone Boundary B/C for at least
Alarm Set Delay ms.
0 – If the largest value of PD v-RMS X, PD v-RMS Y, PD v-RMS Z, PD v-RMS M is
out of the range defined by Severity Zone Boundary A/B and Severity Zone
Boundary B/C for at least Alarm Set Delay ms.
Input
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor