9-8 Accessories & Options
MN1276
The default Baud rate is set to 125 kbit/second and the Node_ID is the drive
1 (AS1 switches 1 to 4).
Note: Every drive, connected to one CAN Bus system must have a different
Node_ID.
After power up you will receive an EMERGENCY message with two data bytes
(0x00 and 0x00) to inform you that the CAN_DRIVE is now active.
Now you will have access to all commands via SDO. If you want to give a
command or set a parameter, you have to put the following message on the
CAN_BUS:
To send a command or set a parameter in the drive:
0x20
Ind_lo
Ind_hi
Sub
XXX
XXX
XXX
XXX
D0
D1
D2
D3
D4
D5
D6
D7
Drive
PC Master
0x20
Ind_lo
Ind_hi
Sub
XXX
XXX
XXX
XXX
ID = 0x600 + NODE_ID <--------------------------------------------
ID = 0x580 + NODE_ID <--------------------------------------------
Where:
X
Data bytes (to write a parameter)
ID
Identifier
0x
Hexadecimal data format
D0 - D7
Data byte 0 to 7 of CAN message
Ind_lo
Low byte of Index of Object dictionary
Ind_hi
High byte of Index of Object dictionary
Sub
Subindex of Object dictionary. If Object has only one entry, Subindex must always be 0
Note: If the first data byte in the returned message from the drive = 0x80, the
commanded action failed.