background image

2-6

MN703

For moderate changes in the maximum speed, there will be a slight effect on the minimum speed 

setting when the minimum is set to zero. There may be significant variation in the minimum speed 

setting if the minimum speed is at a higher than zero setting.

Acceleration Trimpot (ACCEL)  

The ACCEL Trimpot is provided to allow for a smooth start over an adjustable time period each time 

the AC power is applied or the Main Speed Potentiometer is adjusted to a higher speed. The ACCEL 

Trimpot is factory set to 2 seconds, which is the amount of time it will take for the motor to accelerate 

from zero speed to full speed. To increase the acceleration time, rotate the ACCEL Trimpot clockwise. 

To decrease the acceleration time, rotate the ACCEL Trimpot counterclockwise. The ACCEL Trimpot 

range is 0.2 – 10 seconds.

Deceleration Trimpot (DECEL)

 

The DECEL Trimpot controls the amount of rampdown time when the Main Speed Potentiometer is 

adjusted to a lower speed. The DECEL Trimpot is factory set to 2 seconds, which is the amount of 

time it will take for the motor to decelerate from full speed to zero speed. To increase the deceleration 

time, rotate the DECEL Trimpot clockwise. To decrease the deceleration time, rotate the DECEL Trimpot 

counterclockwise. The DECEL Trimpot range is 0.2 – 10 seconds.

Current Limit Trimpot (CL) 

The CL Trimpot is used to limit the maximum current (torque) to the motor. The CL also protects the 

control from excessive current during startup. The CL Trimpot is factory set to 150% of the full load 

current rating of the motor. To increase the current limit, rotate the CL Trimpot clockwise (do not 

exceed 200% of the full load current rating of the motor (maximum clockwise position)). To decrease 

the current limit, rotate the CL Trimpot counterclockwise. On cyclical loads, it may be normal for the 

CL LED to momentarily flash.  

(Visible only if the cover is removed.) The CL Trimpot range is 0% – 200% of the full load current 

rating of the motor. Some application may require a lower value so as not to damage process material 

or drive train components.

Note:  For the Current Limit to operate properly, the correct Plug-In Horsepower Resistor® must be 

installed for the particular motor and input voltage being used.  Calibration of the CL Trimpot is 

normally not required when the proper Plug-In Horsepower Resistor® is installed.

Caution:  do not leave motor shaft locked for more than 2 – 3 seconds or motor damage may result.

To Recalibrate the CL Trimpot: 
1.  Disconnect the AC power and connect a DC ammeter in series with either motor armature lead. 

If only an AC ammeter is available, connect it in series with either AC line input lead.

2.  Set the Main Speed Potentiometer to approximately 30% – 50% clockwise position.
3.  Set the CL Trimpot fully counterclockwise. The CL LED will illuminate red.
4.  Load the motor shaft in accordance with application requirements.
Apply power and rotate the CL Trimpot clockwise until the desired current reading is observed on the 

DC ammeter. Factory Current Limit setting is 150% of the full load current rating of the motor. If using 

an AC ammeter connected in the AC line input, the factory Current Limit setting will read 75% of the 

full load current rating of the motor. Do not exceed 200% of the full load current rating of the motor 

(maximum clockwise position).

IR Compensation Trimpot (IR) 

 

The IR Trimpot sets the amount of compensating voltage required to keep the motor speed constant 

under varying loads. If the load does not vary substantially, the IR Trimpot may be set to a minimum 

level (approximately 1/4 of full clockwise rotation). The IR Trimpot is factory set to provide 3 Volts of 

compensation for controls with 90 Volt DC output and 6 Volts of compensation for controls with 180 

Volt DC Output. To increase the amount of compensating voltage, rotate the IR Trimpot clockwise. To 

decrease the amount of compensating voltage, rotate the IR Trimpot counterclockwise.
To Recalibrate the IR Trimpot:
1.  Set the IR Trimpot to approximately 25% rotation.
2.  Run the motor unloaded at approximately 1/3 speed and record the RPMs.

Summary of Contents for BC140

Page 1: ...6 15 Installation Operating Manual MN703 BC140 BC140 FBR DC CONTROL...

Page 2: ...Any trademarks used in this manual are the property of their respective owners Important Be sure to check www baldor com to download the latest version of this manual in Adobe Acrobat PDF format...

Page 3: ...Motor Armature Connection 2 2 Motor Field Connection Shunt Wound Motors Only 2 2 Full Voltage Field 2 2 Half Voltage Field 2 3 Plug In Horsepower Resistor 2 3 Important Considerations 2 4 Startup Adju...

Page 4: ...ii MN703...

Page 5: ...hock can cause serious or fatal injury WARNING Electrical shock can cause serious or fatal injury Be sure that all power is disconnected and there is no voltage present from this equipment or equipmen...

Page 6: ...here are several things you should do immediately 1 Observe the condition of the shipping container and report any damage immediately to the commercial carrier that delivered your control 2 Verify tha...

Page 7: ...NEMA 1 IP 40 enclosure for indoor use It is recommended that the control be mounted vertically on a flat surface with adequate ventilation Leave enough room below the control to allow for AC line and...

Page 8: ...Cu Recommended Tightening Torque Maximum 50 Ft Maximum 100 Ft AWG mm2 AWG mm2 lb in kg cm 6 1 2 1 16 1 3 14 2 1 12 13 8 12 1 2 14 2 1 12 3 3 12 13 8 The AC Line Fuse acts as a disconnect in case of a...

Page 9: ...e control to the motor so the IR Compensation and Current Limit settings to be correct Select the proper Plug In Horsepower Resistor according to Table 2 3 Plug In Horsepower Resistors are available f...

Page 10: ...he actual AC line amperage of the control at full load should not exceed the motor s DC nameplate rating Torque Requirements The motor selected for the application must be capable of supplying the nec...

Page 11: ...the main power applied an insulated adjustment tool must be used to prevent shock hazard and safety glasses must be worn TRIMPOT ADJUSTMENTS The control contains trimpots which have been factory set...

Page 12: ...rent rating of the motor Some application may require a lower value so as not to damage process material or drive train components Note For the Current Limit to operate properly the correct Plug In Ho...

Page 13: ...ble 2 4 Troubleshooting Guide without Optional Forward Brake Reverse Switch Symptom Possible Cause Suggested Corrective Action Motor is not running and Pilot Light not illuminated On Off AC Line Switc...

Page 14: ...or CL and or IR Trimpots may be set incorrectly Readjust the CL and or IR Trimpots Defective speed control module Replace speed control Voltage Select Switch set to wrong position Recheck line voltage...

Page 15: ...ch CATALOG NO BC144 The optional Forward Brake Reverse Switch Catalog No BC144 is used to dynamically brake the motor and reverse motor direction The switch assembly is to be installed in the mounting...

Page 16: ...03 Optional RFI Filter BC24 LF Panel mount Rated 24 Amps at 115 and 208 230 Volts AC single phase Complies with CE Directive 89 336 EEC EN55022 and or EN55011 relating to the EMC Class A Industrial St...

Page 17: ......

Page 18: ......

Page 19: ...SUITE 400 ROGERS MN 55374 PHONE 763 428 3633 FAX 763 428 4551 MISSOURI ST LOUIS 13678 LAKEFRONT DRIVE EARTH CITY MO 63045 PHONE 314 373 3032 FAX 314 373 3038 KANSAS CITY 9810 INDUSTRIAL BLVD LENEXA KS...

Page 20: ...P O Box 2400 Fort Smith AR 72902 2400 U S A Ph 1 479 646 4711 Fax 1 479 648 5792 International Fax 1 479 648 5895 www baldor com Baldor Electric Company MN703 All Rights Reserved Printed in USA A40244...

Reviews: