background image

40940_N

02-08-19

4

Manufactured under one or more of these patents.  U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 

6590188, 6976052, 6965815, 7030343, 7,417,834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and 

domestic applied for and pending.   All material copyright of Balboa Water Group.

Pumps

Press the “Jets 1” button once to turn pump 1 on or off, and to shift between low- and high-speeds if equipped.  
If left running, the pump will turn off after a time-out period. The pump 1 low-speed will time out after 30 minutes. The 
high-speed will time out after 15 minutes.
On non-circ systems, the low-speed of pump 1 runs when the blower or any other pump is on. If the spa is in Ready Mode 
(See page 6), Pump 1 low may also activate for at least 1 minute every 30 minutes to detect the spa temperature (polling) 
and then to heat to the set temperature if needed. When the low-speed turns on automatically, it cannot be deactivated 
from the panel, however the high speed may be started.

Circulation Pump Modes

If the system is equipped with a circ pump, it will be configured to work in one of three different ways:
1, The circ pump operates continuously (24 hours) with the exception of turning off for 30 minutes at a time when the 
water temperature reaches 3°F (1.5°C) above the set temperature (most likely to happen in very hot climates).
2, The circ pump stays on continuously, regardless of water temperature.
3, A programmable circ pump will come on when the system is checking temperature (polling), during filter cycles, during 
freeze conditions, or when another pump is on.
The specific Circulation Mode that is used has been determined by the Manufacturer and cannot be changed in the field.

Filtration and Ozone

On non-circ systems, Pump 1 low and the ozone generator will run during filtration. On circ systems, the ozone will run with 
the circ pump.
The system is factory-programmed with one filter cycle that will run in the evening (assuming the time-of-day is properly 
set) when energy rates are often lower. The filter time and duration are programmable. (See page 10) 
A second filter cycle can be enabled as needed.
At the start of each filter cycle, the blower (if there is one) or Pump 2 (if there is one) will run briefly to purge its plumb-
ing to maintain good water quality. 

Freeze Protection

If the temperature sensors within the heater detect a low enough temperature, then the pump(s) and the blower automati-
cally activate to provide freeze protection. The pump(s) and blower will run either continuously or periodically depending 
on conditions.
In colder climates, an optional additional freeze sensor may be added to protect against freeze conditions that may not 
be sensed by the standard sensors. Auxiliary freeze sensor protection acts similarly except with the temperature thresholds 
determined by the switch. See your dealer for details.

Clean-up Cycle (optional)

When a pump or blower is turned on by a button press, a clean-up cycle begins 30 minutes after the pump or blower is 
turned off or times out. The pump and the ozone generator will run for 30 minutes or more, depending on the system. On 
some systems, you can change this setting. (See the Preferences section on page 12)

Spa Behavior

Summary of Contents for TP600

Page 1: ...ent 2373248 other patents both foreign and domestic applied for and pending All material copyright of Balboa Water Group TP600 and TP400 Control Panels User Interface and Programming Reference Standar...

Page 2: ...oose button depending on control panel configuration Indicates Alternating or Progressive Message every 1 2 second Waiting time that keeps the last change to a menu item Waiting time depends on menu i...

Page 3: ...As soon as the above display appears on the panel push the Jet button once to start Pump 1 in low speed and then again to switch to high speed Also push the Pump 2 or Aux button if you have a 2nd pump...

Page 4: ...temperature polling during filter cycles during freeze conditions or when another pump is on The specific Circulation Mode that is used has been determined by the Manufacturer and cannot be changed in...

Page 5: ...be used for various reasons with a common use being a ready to use setting vs a vacation setting The Ranges are chosen using the menu structure below Each range maintains its own set temperature as p...

Page 6: ...on and off Pump 1 Low will run until set temperature is reached or 1 hour has passed After 1 hour the System will revert to Rest Mode This mode can also be reset by entering the Mode Menu and changing...

Page 7: ...ystem will still operate and all other user settings will be stored If filter cycles are required to run at a particular time of day resetting the clock will return the filter times to the actual prog...

Page 8: ...DY RANGE FLTR1 SET To Set To next item in Main Menu A Few Seconds A Few Seconds A few seconds RANGE Waiting a few seconds reverts to origianl settings Sub Menu Detail Unlocking the Set Temperature or...

Page 9: ...seconds Main Screen READY RANGE FLTR1 a few seconds or To next item in Main Menu SET Hold Mode M037 Hold Mode is used to disable the pumps during service functions like cleaning or replacing the filte...

Page 10: ...aiting a few seconds reverts to original setting Wait to Revert Waiting a few seconds reverts to original setting Waiting a few seconds will lose any new Filter 1 Start Time and Run Hours and revert t...

Page 11: ...an hour SET A SET A SET A Sets 15 minute increments SET A SET SET SET Shows flashes start time to show RUN HRS to show TIMR ENDS xx xx Sets 15 minute increments A Waiting a few seconds reverts to orig...

Page 12: ...clock between 12 hr and 24 hr display RE MIN DERS Reminders Turn the reminder messages like Clean Filter On or Off CLN UP Cleanup Cleanup Cycle Duration is not always enabled so it may not appear When...

Page 13: ...Light for CLEAN UP 05 15 09 While the Temperature is still flashing press Light repeatedly until PREF appears in the LCD SET RANGE Main Screen READY RANGE FLTR1 To next item in Main Menu UTIL To next...

Page 14: ...he bottom of the screen SSID Software ID Displays the software ID number for the System MODL System Model Displays the Model Number of the System SETP Current Setup Displays the currently selected Con...

Page 15: ...led so it may not appear This screen allows the GFCI to be tested manually from the panel and can be used to reset the automatic test feature If the GFCI Test Feature is reset the device will trip wit...

Page 16: ...ilities appears in the LCD SET RANGE Main Screen READY RANGE FLTR1 SET SET SET When set to ON Panel will display alternate readings from Senor A and Sensor B on Main Screen Back to normal operation DI...

Page 17: ...hin a few seconds and the spa should shut down If it does not shut down the power and manually verify that a GFCI breaker is installed and that the circuit and spa are wired correctly Verify the funct...

Page 18: ...Sensor ATemp Sensor B Temp 24 Fault messages is the maximum Fewer messages may be displayed To FIRST item in Main Menu TEMP Range While the Temperature is still flashing press Light repeatedly until...

Page 19: ...is exited Water is too Hot OHS M029 One of the water temp sensors has detected spa water temp 110 F 43 3 C and spa functions are disabled System will auto reset when the spa water temp is below 108 F...

Page 20: ...y dr M028 Possible dry heater or not enough water in the heater to start it The spa is shut down for 15 min Press any button to reset the heater start up See Flow Related Checks below Heater is Dry M0...

Page 21: ...ut of sync by 2 F or 3 F Call for Service Sensor Balance is Poor M026 The temperature sensors ARE out of sync The Sensor Balance is Poor fault has been established for at least 1 hour Call for Service...

Page 22: ...Failure System Could Not Test Trip the GFCI M036 NORTH AMERICA ONLY May indicate an unsafe installation Contact your dealer or service organization A Pump Appears to have been Stuck ON when spa was la...

Page 23: ...is an important safety device and must be tested on a regular basis to verify its reliability Every user should be trained to safely test the GFCI or RCD associated with the hot tub installation A GF...

Page 24: ...od skirting and furniture should be cleaned and conditioned per the manufacturers instructions for maximum life Appears on a regular schedule e g every 365 days Filters should be replaced occasionally...

Page 25: ...d the instruction manual Adequate drainage must be provided if the equipment is to be installed in a pit For use only within an enclosure rated CSA Enclosure 3 Connect only to a circuit protected by a...

Reviews: