40940_N
02-08-19
4
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370,
6590188, 6976052, 6965815, 7030343, 7,417,834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and
domestic applied for and pending. All material copyright of Balboa Water Group.
Pumps
Press the “Jets 1” button once to turn pump 1 on or off, and to shift between low- and high-speeds if equipped.
If left running, the pump will turn off after a time-out period. The pump 1 low-speed will time out after 30 minutes. The
high-speed will time out after 15 minutes.
On non-circ systems, the low-speed of pump 1 runs when the blower or any other pump is on. If the spa is in Ready Mode
(See page 6), Pump 1 low may also activate for at least 1 minute every 30 minutes to detect the spa temperature (polling)
and then to heat to the set temperature if needed. When the low-speed turns on automatically, it cannot be deactivated
from the panel, however the high speed may be started.
Circulation Pump Modes
If the system is equipped with a circ pump, it will be configured to work in one of three different ways:
1, The circ pump operates continuously (24 hours) with the exception of turning off for 30 minutes at a time when the
water temperature reaches 3°F (1.5°C) above the set temperature (most likely to happen in very hot climates).
2, The circ pump stays on continuously, regardless of water temperature.
3, A programmable circ pump will come on when the system is checking temperature (polling), during filter cycles, during
freeze conditions, or when another pump is on.
The specific Circulation Mode that is used has been determined by the Manufacturer and cannot be changed in the field.
Filtration and Ozone
On non-circ systems, Pump 1 low and the ozone generator will run during filtration. On circ systems, the ozone will run with
the circ pump.
The system is factory-programmed with one filter cycle that will run in the evening (assuming the time-of-day is properly
set) when energy rates are often lower. The filter time and duration are programmable. (See page 10)
A second filter cycle can be enabled as needed.
At the start of each filter cycle, the blower (if there is one) or Pump 2 (if there is one) will run briefly to purge its plumb-
ing to maintain good water quality.
Freeze Protection
If the temperature sensors within the heater detect a low enough temperature, then the pump(s) and the blower automati-
cally activate to provide freeze protection. The pump(s) and blower will run either continuously or periodically depending
on conditions.
In colder climates, an optional additional freeze sensor may be added to protect against freeze conditions that may not
be sensed by the standard sensors. Auxiliary freeze sensor protection acts similarly except with the temperature thresholds
determined by the switch. See your dealer for details.
Clean-up Cycle (optional)
When a pump or blower is turned on by a button press, a clean-up cycle begins 30 minutes after the pump or blower is
turned off or times out. The pump and the ozone generator will run for 30 minutes or more, depending on the system. On
some systems, you can change this setting. (See the Preferences section on page 12)
Spa Behavior