OPERATING PROCEDURES
CONFIGURATION PROCEDURE
5 - 4
WBPEEUI110506A0
must be selected during configuration. The default value is low
(below zero percent). Table
shows what types of errors
cause the transmitter to enter the fail mode.
NOTE: For a transmitter in the normal acting mode, output corre-
sponding to zero-percent input would be four milliamperes and out-
put corresponding to 100-percent input would be 20 milliamperes.
For a transmitter in the reverse acting mode, output corresponding
to zero-percent input would be 20 milliamperes and output corre-
sponding to 100-percent input would be four milliamperes.
Secondary Engineering Units
Secondary engineering units are programmable. These units
are in a free form format of seven characters. Program any
seven characters into the transmitter, such as
MA
or
GAL/HR
.
These units are used in conjunction with the secondary lower
and upper range numeric values.
Use the up arrow and down arrow keys or the decimal number
keys to select the secondary units.
NOTE: The secondary engineering units are left justified when dis-
played on the local LCD. If desired, enter dummy characters to cen-
ter or right justify the display.
Secondary Lower and Upper Range Values
The secondary lower and upper range values of the transmitter
can be set to any range within
±
99999. These ranges can be
monitored by the Type STT terminal or displayed on the
optional LCD of the transmitter. The ranges are a function of
the output of the device. The output can be polled from the
device or displayed on the optional LCD. These ranges have no
effect on the calibration of the transmitter and are used to
report the output of the transmitter in user-defined units.
Cell Temperature Alarm Limits
This sets the alarm limits for the cell temperature. The default
values are -50.00-degrees Celsius and +120.00-degrees Cel-
sius. Program the alarm limits anywhere between these two
values.
Get Config Key
Once a Type PTSP pressure transmitter has been configured,
the configuration that has been loaded into the transmitter
memory may be reviewed by pressing the GET CONFIG key on
the Type STT terminal (refer to the
). The configuration is not stored
in the Type STT terminal memory unless
YES
is chosen when