INSTALLATION
SELECTING DEFAULTS
3 - 8
WBPEEUI110506A0
GROUNDING
Signal wiring may be either ungrounded (floating) or grounded
at any one point in the signal loop. If more than one transmit-
ter is connected to a single power supply, grounding should be
at the supply. The transmitter housing must also be grounded.
A ground terminal is provided inside the electronics housing
(Figs.
SELECTING DEFAULTS
The configuration of process control equipment within a par-
ticular system dictates the response to the controlled process
of that system. Configuration may include such items as
cross-limits, interlocks and alarms dealing with bad quality,
and safety control equipment. Modern electronic process con-
trol equipment based on semiconductor technology is highly
reliable and can be expected to provide long trouble-free ser-
vice. However, component failures that disrupt process control
are still possible. In addition, power line induced failures, fail-
ures caused by human error, static discharge, conducted and
radiated EMI, acts of nature such as lightning strikes, and
accidents can cause disruption of process control.
Refer to
to select defaults for failure conditions.
HAZARDOUS LOCATION INSTALLATIONS (FLAMMABLE ATMOSPHERES)
The Type PTSP Platinum Standard Smart Pressure Transmit-
ter must not be located in a hazardous (classified) location
unless factory marked as suitable for that location. This equip-
ment must be installed and operated according to
4 to 20 mA Transmitter in a Hazardous Location
.