INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 8
I-E96-409A
®
To connect field, serial link and power wiring:
NOTE: Proper polarity of all signals must be maintained.
1. Insure that the ICS module is pulled out far enough to gain
access to the terminal strip.
2. Feed the field and serial link wiring into the terminal strip
area and connect them to the appropriate terminals.
3. Connect a 14 AWG wire from the +24 VDC bus of the termi-
nation mounting unit to the +24 VDC terminal of the ICS
module.
4. Connect a 14 AWG wire from the common bus of the termi-
nation mounting unit to the common terminal of the ICS
module.
5. Insert the module until it locks securely into place.
6. Replace the front cover.
WARNING
If input or output circuits are a shock hazard after disconnect-
ing system power at the power entry panel, then the door of the
cabinet containing these externally powered circuits must be
marked with a warning stating that multiple power sources
exist.
AVERTISSEMENT
Si des circuits d'entree ou de sortie sont alimentes a partir de
sources extrenes, ils presentent un risque de choc electrique
meme lorsque l'alimentation du systeme est debranchee du
panneau d'entree l'alimentation. Le cas echeant, un avertisse-
ment signalant la presence de sources d'alimentation multiples
doit entre appose sur la porte de l'armoire.
CAUTION
It is strongly recommended that
all
power (cabinet, I/O, etc.) be
turned off before doing any termination module wiring. Failure
to do so could result in equipment damage. Do not apply
power until all wire connections are verified.
ATTENTION
Il est fortement recommandé que
toutes
les alimentations
(armoire, E/S, etc.) soient coupées avant d'effectuer quelque
raccord que ce soit sur un carte de raccordement. Un manque-
ment à ces instructions pourrait causer des dommage à
l'équipement. Ne pas rebrancher les alimentations avant
d'avoir vérìfié tous les raccordements.