INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-409A
2 - 3
Configuring Dipswitches
Configure the termination module for the types of inputs and
outputs desired using dipswitches S1 through S5. Tables
show the possible dipswitch settings.
Cable Connections
The NICS01 Controller/Station Termination Module termi-
nates analog and digital I/O signals, and interfaces them
directly to a master/slave module. Figures
, and
show the cables to use and their connections for several differ-
ent applications of the ICS module. Table
and its application. See Figure
for the location of cable
connectors P1, J1 and J2.
Table 2-1. Switch S1, S2, S3 and S4 Settings
Analog Input
Signal Type
Switch Position
1 2 3 4 5 6 7 8
System powered (4-20 mA)
1 1 1 1 1 1 0 0
Externally powered (4-20 mA)
0 0 0 0 1 1 1 1
Single ended voltage (1-5 VDC)
0 0 0 1 0 1 1 1
Differential voltage (1-5 VDC)
0 0 0 0 0 0 1 1
NOTE: 0 represents the OPEN or OFF side of the switch. 1 represents the CLOSED or ON side of
the switch.
Table 2-2. Switch S5 Settings
Analog Output
Signal Type
Switch Position
1,2
1
2
3
4
Both outputs are 1-5 VDC
1
1
1
1
Analog Output 1 is 1-5 VDC,
Analog Output 2 is 4-20 mA
1
1
0
0
Analog Output 1 is 4-20 mA,
Analog Output 2 is 1-5 VDC
0
0
1
1
Both outputs are 4-20 mA
0
0
0
0
NOTES:
1. 0 represents the OPEN or OFF side of the switch. 1 represents the CLOSED
or ON side of the switch.
2. Switch Positions 1 and 2 represent Analog Output 1 and Switch positions 3
and 4 represent Analog Output 2.
Figure 2-2. NICS01 Cable Connections to One Station
IMCOM03/04
IMCIS02
IMQRC01
IMQRS02
NDIS01
NDCS03
IISAC01
NO ANALOG OUTPUT BYPASS CAPABILITY
T00498A
P3
P1
P1
J1
J2
NKTM01
NKTU02/12
NKTD02/12
NICS01