Summary of Contents for Infi 90 NTCU01

Page 1: ... Process Control and Automation Solutions from Elsag Bailey Group E96 417 Serial Interface Termination Unit NTCU01 ...

Page 2: ...MENTS ÉLECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FRÉQUENCE RADIO DES PRÉCAUTIONS DEVRONT ÊTRE PRISES LORS DE L UTILISATION DU MATÉ RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PRÉCAUTIONS À PRENDRE DANS CE CAS SOIENT SIGNALÉES AUX ENDROITS VOULUS DANS VOTRE USINE PERTURBATIONS DU PROCÉDÉ L ENTRETIEN DOIT ÊTRE ASSURÉ PAR UNE PERSONNE QUALIFIÉE EN CONSIDÉRANT L ASPECT SÉCURITAIRE...

Page 3: ...r modem or diagnostic terminal to a INSIM01 Serial Interface Module It provides a place to connect an RS 232 C cable from the computer or terminal This manual explains how to install and use the NTCU01 unit It explains how to install the cables and mount the termination unit ...

Page 4: ... 5 1 Original A 1 through A 5 Original B 1 through B 3 Original Index 1 Original When an update is received insert the latest changed pages and dispose of the super seded pages NOTE On an update page the changed text or table is indicated by a vertical bar in the outer mar gin of the page adjacent to the changed area A changed figure is indicated by a vertical bar in the outer margin next to the f...

Page 5: ... servicing Special Handling This module uses Electrostatic Sensitive Devices ESD AVERTISSEMENTS D ORDRE GÉNÉRAL Environnement de l équipement Ne pas soumettre les composants à une atmosphère corrosive lors du transport de l entreposage ou l utilisation Possibilité de chocs électriques durant l entretien Débrancher l alimentation ou prendre les précautions pour éviter tout contact avec des composan...

Page 6: ...E TERMINATION UNIT 2 2 CABLE INSTALLATION 2 2 Termination Unit Cables 2 2 Communication Cable 2 5 SECTION 3 MAINTENANCE 3 1 INTRODUCTION 3 1 MAINTENANCE SCHEDULE 3 1 SECTION 4 REPAIR REPLACEMENT PROCEDURES 4 1 INTRODUCTION 4 1 TERMINATION UNIT REPLACEMENT 4 1 SECTION 5 SUPPORT SERVICES 5 1 INTRODUCTION 5 1 REPLACEMENT PARTS AND ORDERING INFORMATION 5 1 TRAINING 5 1 TECHNICAL DOCUMENTATION 5 1 APPE...

Page 7: ...ace Module Component Locations B 1 B 2 Jumper Settings for Communication Baud Rates B 3 List of Tables No Title Page 1 1 Nomenclature 1 3 1 2 Glossary of Terms and Abbreviations 1 4 1 3 Reference Documents 1 5 1 4 Specifications 1 5 2 1 TCU Cable Applications 2 5 3 1 Maintenance Schedule 3 1 A 1 Address Switch Settings S2 A 2 A 2 Port Option Switch S3 Settings A 2 A 3 Port Operational Option Switc...

Page 8: ...termination unit into operation until you read and understand this instruction HARDWARE DESCRIPTION The TCU unit mounts on a NFTP01 Field Termination Panel inside the INFI 90 cabinet It is a printed circuit board that consists of Two DB 25 connector sockets Cable connector Current limiting resistors Faston tabs for system common HARDWARE APPLICATION The NTCU01 unit provides a place to connect two ...

Page 9: ...I O and status information FEATURES Current limiting resistors prevent excessive current from flow ing through the RS 232 C cable if there is a significant differ ence of potential between the signal ground of the computer and the signal ground of the INFI 90 components Figure 1 1 The NTCU01 Termination Unit Connecting a Diagnostic Terminal to the INSPM01 Module COMMUNICATION HIGHWAY INFI NET OR P...

Page 10: ...viron mental specifications Installation Section 2 is the installation section It explains physical instal lation wiring and cable requirements Maintenance This section contains a maintenance schedule Repair Replacement Procedures Section 4 contains instructions explaining how to replace the termination unit Support Services Support services cover training documentation and how to order parts from...

Page 11: ...quipment Equipment comprising the data source data sink or both that provides the communication control function In RS 232 C communication systems the DTE nomenclature indicates the signals that appear at specified cable connection contacts Terminals and printers are examples of this type of device FTP Field termination panel A panel inside the INFI 90 cabinet on which to mount termination units H...

Page 12: ...lue Mounting Screw mounts to the field termination panel Cooling Requirements No cooling necessary when used in Bailey cabinets and operated within stated environmental limits Operating Temperature 0 C to 70 C 32 F to 158 F Relative Humidity 5 to 90 5 up to 55 C 131 F noncondensing 5 to 40 5 up to 70 C 158 F noncondensing Air Quality Bailey equipment should be operated and stored in a noncorrosive...

Page 13: ...n the system Save the bag for future use 2 Ground Bag Before Opening Before opening a bag con taining an assembly with CMOS devices touch it to the equip ment housing or a ground to equalize charges 3 Avoid Touching Circuitry Handle assemblies by the edges avoid touching the circuitry 4 Avoid Partial Connection of CMOS device Verify that all devices connected to the modules are properly grounded b...

Page 14: ...board into the proper slots of the termination panel standoff see Figure 2 1 and slide the circuit board into position 2 Secure the termination unit circuit board to the field termi nation panel with two number 10 screws see Figure 2 1 3 Connect the chassis ground to the field termination panel by installing a number 10 self tapping sheet metal screw and star washer through E2 on the TCU circuit b...

Page 15: ...ay from the MMU backplane several inches The card edge of the module must not come into contact with the card edge connector of the termination cable while installing the cable After installing the cable slide the module into the MMU slot so that the card edge sits within the card edge connector Refer to the prod uct instructions for the INSIM01 or IMSPM01 for more information about the installati...

Page 16: ... 3 TCU Cable Connection to the SIM Module NTCU01 COMPUTER PORT P3 DIAGNOSTIC PORT P2 NSM P1 E2 CHASSIS GROUND E1 SYSTEM COMMON T00593A INSIM01 NKTU01 11 P1 P3 P1 NTCU01 T00594A ALTERNATE CONNECTION POINT FOR COMPUTER OR MODEM PORT 2 TO DIAGNOSTIC MONITOR PORT 1 RS 232 CABLE RS 232 CABLE P3 P2 ...

Page 17: ...al interface termination unit is OFF before installing the RS 232 C cable 1 Connect the RS 232 C cable to the termination unit at P2 port one or P3 port two 2 The other end of the cable connected to P3 port two con nects to a computer or modem 3 The other end of the cable connected to P2 port one con nects to a diagnostic terminal 4 Attach a 14 AWG wire from the DC common bus bar at the bottom of ...

Page 18: ...na tion unit Figure 2 4 RS 232 C Compatible Cable Wiring Requirements CHASSIS GND TX RX RTS CTS DSR SIG GND DCD DTR CHASSIS GND TX RX RTS CTS DSR SIG GND DCD DTR CHASSIS GND TX RX RTS CTS DSR SIG GND DCD DTR CHASSIS GND TX RX RTS CTS DSR SIG GND DCD DTR 1 2 3 4 5 6 7 8 20 1 2 3 4 5 6 7 8 20 1 2 3 4 5 6 7 8 20 1 2 3 4 5 6 7 8 20 NTCU01 DCE NTCU01 DCE DATA TERMINAL EQUIPMENT DATA COMMUNICATION EQUIP...

Page 19: ... only qualified per sonnel should perform maintenance MAINTENANCE SCHEDULE Table 3 1 is the maintenance schedule These tasks are to be performed at the specified intervals Table 3 1 Maintenance Schedule Task Interval Clean and tighten all cable and power connections Every 6 months or during plant shutdown whichever occurs first Use a static safe vacuum cleaner to remove dust from Termination units...

Page 20: ... 232 C cable 1 Disconnect the RS 232 C cable from the termination unit 2 Disconnect the termination unit cable from the P1 socket on the termination unit 3 Remove and save the chassis ground screw with star washer and the two mounting screws that secure the termina tion unit to the field termination panel 4 Remove the faulty termination unit 5 Insert the tabs of the replacement termination unit in...

Page 21: ...is information 1 Part description part number and quantity 2 Model and serial numbers if applicable 3 Bailey Controls instruction manual number page number and reference figure that identifies the part Order parts without commercial descriptions from the nearest Bailey Controls office TRAINING Bailey Controls has a modern training facility available for training of your personnel On site training ...

Page 22: ...switch settings S3 Table A 3 contains the port opera tional switch S4 settings Jumper settings that set up to mod ule handshaking and baud rate are covered in the text These jumpers should be set to match the RS 232 C cable require ments explained in Section 2 See Figure 2 4 for the RS 232 C cable wiring requirements Refer to the IMSPM01 instruction for more detailed installation and configuration...

Page 23: ...1 0 22 1 0 1 1 0 7 0 0 1 1 1 23 1 0 1 1 1 8 0 1 0 0 0 24 1 1 0 0 0 9 0 1 0 0 1 25 1 1 0 0 1 10 0 1 0 1 0 26 1 1 0 1 0 11 0 1 0 1 1 27 1 1 0 1 1 12 0 1 1 0 0 28 1 1 1 0 0 13 0 1 1 0 1 29 1 1 1 0 1 14 0 1 1 1 0 30 1 1 1 1 0 15 0 1 1 1 1 31 1 1 1 1 1 NOTE 1 Open Off 0 Closed On Table A 2 Port Option Switch S3 Settings Dipswitch Position Data Bits Stop Bits Type Parity 2 3 4 0 0 0 7 2 Even 0 0 1 7 2 O...

Page 24: ...ments The jumper settings depend on the equipment being used with the SPM module For an explana tion of the handshaking signals or further explanation about the serial port configuration refer to the IMSPM01 Serial Port Module instruction manual NOTE This appendix identifies all RS 232C handshaking signals with respect to the DTE device Jumpers JP1 and JP2 are factory installed ROM compatibility j...

Page 25: ... forced to other voltage levels that would change the logic state and disable the ACIA circuit Jumpers JP4 JP6 Jumpers JP4 and JP6 are for the data terminal ready DTR handshaking lines of the RS 232C serial ports JP4 for port 1 and JP6 for port 2 These are inputs to the serial port module It uses this signal to verify that a DTE device is connected and that a communication link is to be maintained...

Page 26: ...n point Bailey Controls software does not provide these signals When the SPM module is connected to Bailey Controls equipment place a jumper across pins 1 and 2 of JP11 and JP12 This sets the output lines at 12 VDC For applications requiring this output place the jumpers across pins 2 and 3 of JP11 or JP12 This causes the SPM module to output a logic 1 when the MFT circuit is normal and the ACIA c...

Page 27: ...ists the opera tions option switch settings for SW4 These operations option switch apply to circuit boards that have firmware revision F or higher Dipswitches SW2 and SW4 pole 4 only determine the SIM module computer port address Table B 2 shows how the 6 bit binary address is defined Table B 3 lists the computer diag nostic port data characteristics SW3 Earlier versions of the INSIM01 module have...

Page 28: ...address refer to Table B 2 NOTE 1 Open Off 0 Closed On Table B 2 SW2 Computer Port Address Computer Port Address Definition1 SW4 Pole SW2 Pole Number MSB LSB 4 1 2 3 4 5 Address SW4 pole 4 SW2 poles 1 through 5 X X X X X X NOTE 1 Only valid when SW4 pole 3 1 SIM computer port address select protocol enabled Table B 3 Computer Diagnostic Port Options SW3 Data Characteristics Option SW3 Position Num...

Page 29: ...r to send CTS data set ready DSR and data carrier detect DCD handshaking lines These lines are not required by the SIM module Shorting pins 2 and 3 by placing a jumper across them ties these signals to 12 VDC Table B 4 Handshaking Signal Options Bypass Options Jumper Settings JP3 JP4 JP5 JP6 Not allowed 1 to 2 Diagnostic terminal not required to provide RTS 2 to 3 Enable DTR from diagnostic termin...

Page 30: ...switch and jumper settings A 1 Jumper configuration A 3 Installation Communication cable 2 5 Termination unit 2 2 Termination unit cable 2 2 M Maintenance 3 1 Mounting the termination unit 2 2 N Nomenclature 1 3 O Ordering information 5 1 R Reference documents 1 5 Replacement procedure 4 1 S Special handling 2 1 Specifications 1 5 T Termination unit cable Installation 2 2 Lengths 2 5 Termination u...

Page 31: ...8756 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefax 39 10 6582 941 GERMANY Graefstrasse 97 D 60487 Frankfurt Main Germany Telephone 49 69 799 0 Telefax 49 69 799 2406 Form I E96 417A Litho in U S A 1092 Copyright 1992 by Elsag Bailey Process Automati...