background image

Page 4 from 6 
E110003813092 

M-Bus Interface Module XC 

User Manual

 

 

Bär Industrie-Elektronik GmbH 

 Rathsbergstr. 23 

 D-90411 Nürnberg 

 Phone +49 911 970590 

 Fax +49 911 9705950 

 

 

Technical data: 

Housing: 

Polycarbonate housing with terminals for using with EMH LZQJ-XC and 
DMTZ-XC meters for residential and industrial applications 

Degree of protection: 

IP20 (according to IEC 60529) 

Protection class: 

Dimensions: 

50mm x 105mm x 27mm (W x H x D) 

Nominal voltage: 

Internal power supply from LZQJ-XC or DMTZ-XC meter 

M-Bus load 

1,9mA 

Installation: 

exchangeable during the meter operation 

Temperature range: 

-25°C to +55°C (operational) 
-40°C to +80°C (storage temperature) 

Relative humanity: 

0..95%, non-condensing 

LED displays: 

2 LED

’s:  

  

(green) Tx: transmit data 

 

  

(yellow) Rx: receive data 

Interface: 

M-Bus (2 wires, passive) according to EN 13757-2 (physical layer) 

alternative: BFC-Bus (BAER Filed Control, 56VDC)  

Baud rate: 

300 to 9600 baud (fixed baud rate) 

Data format: 

IEC 62056-21: 7E1 

DLMS: 8N1 

Data readout: 

Transparent data readout suitable for all common control centers 
Note: it is a transparent M-Bus level converter without protocol 
conversion 

Transmission protocol: 

IEC 62056-21 (conform to VDEW2+) with fixed baud rate (OBIS 
Codes) or DLMS (option) 

 