Inputs/Outputs
Analog Output
Range
[4 to 20 mA]
S
This parameter establishes the range of the analog output signal. To change Analog
Output range, follow these steps from the
Inputs/Outputs menu
:
1. Select
Analog Output
to view the Analog Output display.
2. Select one of the following options:
• 4 to 20 mA
• 0 to 20 mA
• 2 to 10 mA
• 0 to 10 mA
3. Press
[E]
to save the analog output and return to the Inputs/Outputs menu.
Alarm Mode
[HIGH]
S
This parameter configures the behavior of the analog output during alarm conditions.
Three options exist for this parameter:
OFF, LOW, and HIGH.
OFF:
Analog signal is based on flow rate and always within the configured range
LOW:
During alarm conditions, the analog signal will be 2mA less than the
configured lower range
HIGH:
During alarm conditions, the analog signal will be 2mA more than the
configured upper range
For example, if the analog range is 4 to 20 mA and the alarm mode is set to HIGH, then
during a full scale flow alarm condition, the analog output current will be 22 mA.
To change the analog output alarm mode, follow these steps from the Inputs/Outputs
menu:
1. Select
Alarm Mode
to view the Alarm Mode display.
2. Select one of the following options:
• OFF
• LOW
• HIGH
3. Press
[E]
to save the alarm mode and return to the Inputs/Outputs menu.
Digital Input
Digital input lets you configure the functional operation of the digital input. The following functions
are supported:
• Remote Reset – Clears totalizer T2 (uni-directional)
• Batch Reset – Resets batch totalizer PS to preset amount and clears T2 (uni-directional)
• Pos Zero Return – Forces flow rate to zero (does not totalize)
To change Digital Input, follow these steps from the
Inputs/Outputs menu
:
1. Select
Digital Input
to view the Digital Input display.
2. Select the desired function.
3. Press
[E]
to save the digital input and return to the Inputs/Outputs menu.