Programming Procedures
Exponent
Totalizer Multiplier
E-2
× 001
(
÷100)
E-1
× 01
(
÷100)
E0
× 1 (no multiplier)
E1
× 10
E2
× 100
E3
× 1000
E4
× 10,000
E5
× 100,000
E6
× 1,000,000
Table 4: Total flow units
Full Flow Rate (FULL FLOW)
The
Full Flow Rate
parameter is used to span the meter Edit with the
Zero Capture (ZERO CAP)
You must set the zero position of the meter cone when installing the meter To capture the
zero calibration position, press
ENTER
at the
ZERO CAP
prompt "NO" displays Press either
arrow key to change to "YES"
,
then press
ENTER
to capture zero
Viscosity Units (VIS UNIT) (Displayed for OIL meters only)
The
Viscosity Units
parameter is used in conjunction with
Viscosity
to perform viscosity
correction for oil applications You can select the viscosity units, SUS or cSt Edit with the
"List Item Selection Procedure" on page 15
Viscosity (VISCOSITY) (Displayed for OIL meters only)
Viscosity
is used in conjunction with
Viscosity Units
to perform viscosity correction for oil
applications Enter the viscosity in either SUS or cSt, depending on the viscosity units
selected for the oil being used Edit with the
"Numeric Value Entry Procedure" on page 15
Operating Pressure Unit (PRES UNIT) (Displayed for GAS Meters Only)
The
Operating Pressure Units
parameter is used in conjunction with
Operating Pressure
in
gas applications to compensate for the actual pressure being measured at the meter The
operating pressure unit selections are Bar or PSI Edit with the
"List Item Selection Procedure"
Page 17
September 2017
XMT-UM-00498-EN-03