POOGOAMMING
Each turbine flow meter is shipped with either a K-factor value or frequency data If frequency data is provided, the data must
be converted to a K-factor before programming the monitor K-factor information, when supplied, can usually be found on the
neck of the flow meter or stamped on the flow meter body The K-factor represents the number of pulses per unit of volume
The K-factor is needed to program the monitor readout
Programming Mode
K Factor Units
Units
Pulse Output
IO/SETUP
METER
PUL/GAL
PUL/FT3
PUL/LTR
PUL/M3
K FACTOR
GPM/GAL LPM/LIT
M3PH/M3 M3PD/M3 BPD/BBL
DSP
BOTH TOTAL RATE
TEST
PULS ON PULS OFF
PASSWORD
RST PSWD
Enter Program Mode
Press
MENU
to enter the programming mode The mode indicator changes from
RUN
to
PROGRAM
Select Meter Size
At the
METER
prompt, press
UP
or
OIGHT
to scroll to the bore size of your meter Press
ENTEO
to save and advance to the
K-factor Units
parameter
OTEE:
N
The meter connection size and the bore size are different For example, many of the one inch NPT turbines have bore
sizes that range from 3/8…1 in Be sure to use the correct bore size or the meter will report incorrect flows and totals
Enter The K-Factor Unit
Press
UP
or
OIGHT
to scroll to the K-factor unit of the meter Enter the unit that the meter was calibrated in
Example
If the meter was calibrated in US gallons, use
PUL/GAL
Press
ENTEO
to save the K-factor unit and advance to the
K FACTOR
parameter
OTEE:
N
Unless otherwise specified, Blancett turbine flow meters are supplied with K-factors measured in pulses per gallon
(
PUL/GAL
) which will automatically convert to your desired units of measure
Enter The Meter's K-Factor
OTEE:
N
The K-factor supplied with the meter or calculated from calibration data is needed to set this parameter
To change the K-factor value, press
OIGHT
to select the digit that you wish to change Press
UP
to increment the digit until it
matches the meter’s K-factor Repeat this process until all K-factor digits have been entered Press
ENTEO
to save the K-factor
and advance to
RATE/TOTAL
Programming
Page 8
March 2017
DSY-PM-00277-EN-03