ADDITIONAL INPUT OPTIONS

The Blancett flow monitor is capable of receiving magnetic pickup input or a contact closure input  Since most Blancett flow 

meters use a magnetic pickup, the monitor is shipped configured for magnetic pickup input  To change to a contact closure 

input, remove JP2 from the bottom two pins and jumper them to the top two pins  See image below 

D

1.5 V

OL

TS

C

A

UTION DO NO

T C
ONNEC

T IMPR

OPERL

Y

CHANGE OR DISPOSE OF IN FIRE

. BA
TTER

M

AY EXPL

ODE OR LEAK

.   M
ADE IN U

.S.A.

ALK
ALINE BA

TTER
Y

Pulse Out

Freq. In

4-20 mA

+ - + - + -

External

Totalizer Reset

10k

30V DC (Max)

20 mS Pulse

N/C N/C

Mag

Input

Pulse

Inuput

TB2 Reset

Pulse Out

Freq. In

4-20 mA

+ - + - + -

External

Totalizer Reset

10k

30V DC (Max)

20 mS Pulse

Mag

Input

Pulse

Inuput

TB2 Reset

10…30V DC 

1…5V DC 

250 Typ

O

MAX

  = 

(Loop Supply Voltage - 5)

0.02

Battery Power

Loop Power

BATTEOY OEPLACEMENT

Battery powered monitors use a single 1 5V, D size alkaline battery  When replacement is necessary, use a clean fresh battery 

for continued trouble-free operation  Save the total to memory before removing the battery 

DO NOT OPEN EXPLOSION PROOF ENCLOSURE UNLESS THE AREA IS KNOWN TO BE FREE OF HAZARDS. FAILURE 

TO MAKE THE AREA SAFE BEFORE OPENING THE ENCLOSURE CAN RESULT IN A HAZARDOUS SITUATION WITH A 

POTENTIAL FOR INJURY.

1   Carefully unscrew the enclosure cover to access the circuit board  
2   Remove the four screws securing the circuit board to the enclosure  
3   Lay the circuit board to the side being careful not to pull any wires from their connections  
4   Clip the battery retaining wire/strap and remove the battery  
5   Replace the battery, being sure to observe the proper polarity and install a new retaining strap or wire  
6   Reassemble the monitor, reversing the disassembly process 

Additional Input Options

Page 11 

March 2017 

DSY-PM-00277-EN-03

Summary of Contents for B280-737

Page 1: ...Flow Monitor B2800XP Explosion Proof Flow Monitor Standard DSY PM 00277 EN 03 March 2017 User Manual...

Page 2: ...s 7 Modes 7 Programming 8 Programming Mode 8 Run Mode 9 Additional Scaling Parameters 10 Flow 4 mA Setting 10 Flow 20 mA Setting 10 4 20 mA Calibration 10 4 20 mA Test 10 Additional Input Options 11 B...

Page 3: ...serious personal injury Indicates a hazardous situation which if not avoided could result in severe personal injury or death Indicates a hazardous situation which if not avoided is estimated to be ca...

Page 4: ...provides for selectable units viewing in run mode and prompts for variables in program mode The display can show rate total or alternate between both rate and total Programming Buttons MENU ENTER EXPL...

Page 5: ...amage to the cover threads and glass lens when glass lens cover is used 5 Pull wires into enclosure making certain they are long enough to make the required connections and to remove the instrument or...

Page 6: ...kits are available Hub Size Kit Number Meter Sizes 1 2 in NPT Hub B280 742 3 8 in 1 2 in 3 4 in with 1 2 in NPT End Fittings 1 in NPT Hub B280 737 All Sizes with 1 in NPT End Fittings and Larger Insta...

Page 7: ...programming the display with the necessary information turn on the lock out feature to prevent unauthorized access or changing the meter s setup parameters MENU ENTER Buttons MENU Switches to PROGRAM...

Page 8: ...and the bore size are different For example many of the one inch NPT turbines have bore sizes that range from 3 8 1 in Be sure to use the correct bore size or the meter will report incorrect flows and...

Page 9: ...e Initially the password is set to all zeros and any user can modify the parameter settings in PROGRAM mode To change the password enter any four digit code Press UP to increment the digit and RIGHT t...

Page 10: ...tting is typically between 35 50 To set the 4 mA value connect an ammeter in series with the loop power supply At the 4MA OUT prompt press UP to increment and RIGHT to decrement the 4 mA value to unti...

Page 11: ...ttery Power Loop Power BATTERY REPLACEMENT Battery powered monitors use a single 1 5V D size alkaline battery When replacement is necessary use a clean fresh battery for continued trouble free operati...

Page 12: ...r 2 Perform visual electrical and mechanical checks on all components on a regular basis a Visually check for undue heating evidenced by discoloration of wires or other components damaged or worn part...

Page 13: ...nitor pig tail This should stop the noise If not then try reorientating the meter to a new location Flow rate indicator bounces This usually indicates a weak signal Replace pickup and or check all con...

Page 14: ...drop 0 1 A Magnetic Pickup Inputs Frequency Range 0 3500 Hz Trigger Sensitivity 30 mV p p Over Voltage Protected 30V DC Frequency Measurement Accuracy 0 1 Temperature Drift 50 ppm C maximum Optional...

Page 15: ...2 6 in 9 84 mm 5 16 in 1 19 mm 4 51 in 17 07 mm PART NUMBER INFORMATION Program Level S B 28 S X X X X Power Option B Battery L Loop Mounting Style X Explosion proof Units of Measure AB Gallons ED Bar...

Page 16: ...Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfantego 6 44 193 Knur...

Reviews: