INSTALLATION

ELECTRICAL POWER MUST BE TURNED OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE.

1   EIH Instrument enclosures are furnished with 3/4 inch NPT offset through feed cast hubs for conduit entries  (Use Cooper 

Crouse-Hinds RE21-SA to reduce to 1/2 inch hubs )

2   Secure the enclosure to the conduit system  If the enclosure has mounting feet, select a mounting location that will 

provide sufficient strength and rigidity to support the enclosure as well as the enclosed device and wiring 

SELECT A MOUNTING LOCATION SO THAT THE ENCLOSURE WILL NOT BE SUBJECTED TO IMPACT BY HEAVY OBJECTS. 

IMPACTS CAN DAMAGE ENCLOSED DEVICES OR GLASS LENS.

3   Install Cooper Crouse-Hinds EYS sealing fittings required by Section 501-5 and/or 502-5 of the National Electrical Code and 

Section 18 of the Canadian Electrical Code or any other applicable local codes and when enclosure is installed in Class I 

Group B hazardous locations  (For CSA Group C applications, unsealed conduit lengths must not exceed 

five feet or 152 cm )

THE HAZARDOUS LOCATION INFORMATION SPECIFYING CLASS AND GROUP LISTING OF EACH INSTRUMENT 

ENCLOSURE IS MARKED ON THE NAMEPLATE OF EACH ENCLOSURE.

ALL UNUSED CONDUIT OPENINGS MUST BE PLUGGED.  PLUG UNUSED CONDUIT OPENINGS WITH COOPER CROUSE-

HINDS PLG2. PLUGS MUST BE A MINIMUM OF 1⁄8 INCH THICK AND ENGAGE A MINIMUM OF FIVE FULL THREADS.

4   Unthread instrument (and power side) covers and carefully set aside to prevent damage to the cover threads and glass 

lens (when glass lens cover is used) 

5   Pull wires into enclosure making certain they are long enough to make the required connections and to remove the 

instrument or power supply if servicing is required  Install instrument and power supply, if applicable, and make all 

electrical connections 

OTEE:

N

When installing device, be sure to check instrument dimensions to avoid interference with clamping ring on glass 

lens and the cover on standard units 

6   Test wiring for correctness by checking continuity and also check for unwanted grounds with insulator resistance tester  

Make sure test equipment being used will not damage instrument to be housed in the EIH Instrument enclosure 

7   Carefully re-thread cover to enclosure housing  Tighten cover until cover flange contacts body face 

USE CARE TO PREVENT DIRT, GRIT OR OTHER FOREIGN MATERIAL FROM LODGING ON THREADS. IF SUCH MATERIAL 

SETTLES ON THREADS, CLEAN WITH KEROSENE OR STODDARD SOLVENT*, THEN RE-LUBRICATE WITH COOPER 

CROUSE-HINDS TYPE STL THREAD LUBRICANT.

8   Tighten cover set screws to prevent cover from loosening under vibration 

* TO AVOID THE POSSIBILITY OF AN EXPLOSION, OXIDATION AND CORROSION, DO NOT USE GASOLINE OR SIMILAR 

SOLVENT.

TO MAINTAIN THE EXPLOSION PROOF INTEGRITY OF THE ENCLOSURE WITH A SCREW IN A TAPPED MOUNTING PAD 

HOLE, THERE MUST BE A MINIMUM OF 1⁄16 INCH OF MATERIAL BETWEEN THE DRILL POINT AND THE BACK WALL. IF 

FOR ANY REASON A SCREW WILL NOT BE THREADED INTO THE DRILLED HOLE, A MINIMUM OF 1⁄8 INCH OF MATERIAL 

MUST REMAIN BETWEEN THE DRILL POINT AND THE BACK WALL.

Installation

Page 5 

March 2017 

DSY-PM-00277-EN-03

Summary of Contents for B280-737

Page 1: ...Flow Monitor B2800XP Explosion Proof Flow Monitor Standard DSY PM 00277 EN 03 March 2017 User Manual...

Page 2: ...s 7 Modes 7 Programming 8 Programming Mode 8 Run Mode 9 Additional Scaling Parameters 10 Flow 4 mA Setting 10 Flow 20 mA Setting 10 4 20 mA Calibration 10 4 20 mA Test 10 Additional Input Options 11 B...

Page 3: ...serious personal injury Indicates a hazardous situation which if not avoided could result in severe personal injury or death Indicates a hazardous situation which if not avoided is estimated to be ca...

Page 4: ...provides for selectable units viewing in run mode and prompts for variables in program mode The display can show rate total or alternate between both rate and total Programming Buttons MENU ENTER EXPL...

Page 5: ...amage to the cover threads and glass lens when glass lens cover is used 5 Pull wires into enclosure making certain they are long enough to make the required connections and to remove the instrument or...

Page 6: ...kits are available Hub Size Kit Number Meter Sizes 1 2 in NPT Hub B280 742 3 8 in 1 2 in 3 4 in with 1 2 in NPT End Fittings 1 in NPT Hub B280 737 All Sizes with 1 in NPT End Fittings and Larger Insta...

Page 7: ...programming the display with the necessary information turn on the lock out feature to prevent unauthorized access or changing the meter s setup parameters MENU ENTER Buttons MENU Switches to PROGRAM...

Page 8: ...and the bore size are different For example many of the one inch NPT turbines have bore sizes that range from 3 8 1 in Be sure to use the correct bore size or the meter will report incorrect flows and...

Page 9: ...e Initially the password is set to all zeros and any user can modify the parameter settings in PROGRAM mode To change the password enter any four digit code Press UP to increment the digit and RIGHT t...

Page 10: ...tting is typically between 35 50 To set the 4 mA value connect an ammeter in series with the loop power supply At the 4MA OUT prompt press UP to increment and RIGHT to decrement the 4 mA value to unti...

Page 11: ...ttery Power Loop Power BATTERY REPLACEMENT Battery powered monitors use a single 1 5V D size alkaline battery When replacement is necessary use a clean fresh battery for continued trouble free operati...

Page 12: ...r 2 Perform visual electrical and mechanical checks on all components on a regular basis a Visually check for undue heating evidenced by discoloration of wires or other components damaged or worn part...

Page 13: ...nitor pig tail This should stop the noise If not then try reorientating the meter to a new location Flow rate indicator bounces This usually indicates a weak signal Replace pickup and or check all con...

Page 14: ...drop 0 1 A Magnetic Pickup Inputs Frequency Range 0 3500 Hz Trigger Sensitivity 30 mV p p Over Voltage Protected 30V DC Frequency Measurement Accuracy 0 1 Temperature Drift 50 ppm C maximum Optional...

Page 15: ...2 6 in 9 84 mm 5 16 in 1 19 mm 4 51 in 17 07 mm PART NUMBER INFORMATION Program Level S B 28 S X X X X Power Option B Battery L Loop Mounting Style X Explosion proof Units of Measure AB Gallons ED Bar...

Page 16: ...Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfantego 6 44 193 Knur...

Reviews: