TOOUBLESHOOTING GUIDE

Issue

Oemedy

No LCD display

•  Battery Powered Version: Check battery voltage  Should be 1 5V DC  Replace if low or bad 
•  Loop Powered Version: Check for current flow in the loop  Check polarity of the current loop 

connections for proper orientation 

No rate or total 

displayed

•  Check connection from meter pickup to display input terminals 
•  Check turbine meter rotor for debris  Rotor should spin freely 
•  Check programming of flow monitor 
•  Check to see that the minimum flow rate is being met for the current meter in use  Otherwise, 

the flow meter will not accurately send pulses to the flow monitor 

Flow rate display 

interprets reading 

constantly

•  This is usually an indication of external noise  Keep all AC wires separate from DC wires 
•  Check for large motors close to the meter pickup 
•  Check for radio antenna in close proximity 
•  Try disconnecting the pickup from the monitor pig tail  This should stop the noise  If not, then 

try reorientating the meter to a new location 

Flow rate indicator 

bounces

•  This usually indicates a weak signal  Replace pickup and/or check all connections 
•  Check K-factor 

Default K-Factor Values

Meter Size

Default K-Factor

Lower Limit

Upper Limit

3⁄8 in  (9 53 mm)

20,000

16,000

24,000

1/2 in  (12 7 mm)

13,000

10,400

15,600

3/4 in  (19 05 mm)

2750

2200

3300

7⁄8 in  (22 23 mm)

2686

2148

3223

1 in  (25 4 mm)

870 0

686 0

1044

1-1/2 in  (38 1 mm)

330 0

264 0

396 0

2 in  (50 8 mm)

52 0

41 6

62 0

3 in  (76 2 mm)

57 0

45 6

68 0

4 in  (101 6 mm)

29 0

23 2

35 0

6 in  (152 4 mm)

7 0

5 6

8 0

8 in  (203 2 mm)

3 0

2 4

4 0

10 in  (254 mm)

1 6

1 3

2 0

Oeplacement Parts

Component

Part Number

Enclosure

B280635

Battery

B280601

Battery Holder

B280634

Battery Tie Wrap

B228036

Cap Plug 3/8 inch

B118236

Desiccant Pouch

B220141

Pickup Cable

B222-121

Battery Mount Plate

B280618

Adapter Bridge Plate

B280677

Hex Standoffs

B280667

Meter Mount Kit - For 1 inch Hub

B280-737

Meter Mount Kit - For 1/2 inch Hub

B280-742

Troubleshooting Guide

Page 13 

March 2017 

DSY-PM-00277-EN-03

Summary of Contents for B280-737

Page 1: ...Flow Monitor B2800XP Explosion Proof Flow Monitor Standard DSY PM 00277 EN 03 March 2017 User Manual...

Page 2: ...s 7 Modes 7 Programming 8 Programming Mode 8 Run Mode 9 Additional Scaling Parameters 10 Flow 4 mA Setting 10 Flow 20 mA Setting 10 4 20 mA Calibration 10 4 20 mA Test 10 Additional Input Options 11 B...

Page 3: ...serious personal injury Indicates a hazardous situation which if not avoided could result in severe personal injury or death Indicates a hazardous situation which if not avoided is estimated to be ca...

Page 4: ...provides for selectable units viewing in run mode and prompts for variables in program mode The display can show rate total or alternate between both rate and total Programming Buttons MENU ENTER EXPL...

Page 5: ...amage to the cover threads and glass lens when glass lens cover is used 5 Pull wires into enclosure making certain they are long enough to make the required connections and to remove the instrument or...

Page 6: ...kits are available Hub Size Kit Number Meter Sizes 1 2 in NPT Hub B280 742 3 8 in 1 2 in 3 4 in with 1 2 in NPT End Fittings 1 in NPT Hub B280 737 All Sizes with 1 in NPT End Fittings and Larger Insta...

Page 7: ...programming the display with the necessary information turn on the lock out feature to prevent unauthorized access or changing the meter s setup parameters MENU ENTER Buttons MENU Switches to PROGRAM...

Page 8: ...and the bore size are different For example many of the one inch NPT turbines have bore sizes that range from 3 8 1 in Be sure to use the correct bore size or the meter will report incorrect flows and...

Page 9: ...e Initially the password is set to all zeros and any user can modify the parameter settings in PROGRAM mode To change the password enter any four digit code Press UP to increment the digit and RIGHT t...

Page 10: ...tting is typically between 35 50 To set the 4 mA value connect an ammeter in series with the loop power supply At the 4MA OUT prompt press UP to increment and RIGHT to decrement the 4 mA value to unti...

Page 11: ...ttery Power Loop Power BATTERY REPLACEMENT Battery powered monitors use a single 1 5V D size alkaline battery When replacement is necessary use a clean fresh battery for continued trouble free operati...

Page 12: ...r 2 Perform visual electrical and mechanical checks on all components on a regular basis a Visually check for undue heating evidenced by discoloration of wires or other components damaged or worn part...

Page 13: ...nitor pig tail This should stop the noise If not then try reorientating the meter to a new location Flow rate indicator bounces This usually indicates a weak signal Replace pickup and or check all con...

Page 14: ...drop 0 1 A Magnetic Pickup Inputs Frequency Range 0 3500 Hz Trigger Sensitivity 30 mV p p Over Voltage Protected 30V DC Frequency Measurement Accuracy 0 1 Temperature Drift 50 ppm C maximum Optional...

Page 15: ...2 6 in 9 84 mm 5 16 in 1 19 mm 4 51 in 17 07 mm PART NUMBER INFORMATION Program Level S B 28 S X X X X Power Option B Battery L Loop Mounting Style X Explosion proof Units of Measure AB Gallons ED Bar...

Page 16: ...Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfantego 6 44 193 Knur...

Reviews: