Badger Meter 220BR Installation & Operation Manual Download Page 5

Installation & Operation Manual

The alignment of the impeller with the flow in the pipe 
is accomplished by aligning the two “sight holes” at the 
top of the sensor tube assembly with the center line of 
the pipe. 

Make sure the alignment is made to the pipe 

and not to a wall or surface near the sensor. 

To adjust, 

loosen the two set screws in the positioning collar with 
a 3/32 inch Allen wrench provided in the Series 200 hot 
tap installation kit. Slip one end of the 1/4 inch x 18 inch 
steel rod (also supplied in the installation kit) through the 
holes in the sensor tube. Rotate the sensor tube until the 
rod is centered on the pipe. Ensure the flow label “Arrow” 
on the sensor matches the liquid flow direction. Tighten 
the positioning collar Allen screws to lock the sensor 
tube assembly in position. Note: As a backup to the flow 
direction arrow label on the tube assembly, there is a 
smaller hole located beside one of the sighting holes in 
the tube, to also indicate the upstream side of the tube 
assembly.

If the Pipe is Depressurized and Drained

1.  Drill or cut a 1-7/8 inch hole in the pipe with a drill 

or hole saw. Note the pipe wall thickness for use in 
calculating sensor assembly depth. A location on the 
top of the pipe is best for overall performance and 
service life;  however, any radial location on the top 
half of the pipe is acceptable. Allow a minimum of ten 
pipe diameters upstream and five downstream from 
the sensor of straight unobstructed pipe to allow full 
development of the flow profile.

2.  Install either a service saddle or welded pipe fitting (2 

inch female NPT) on the outside diameter of the pipe 
over the 1-7/8 inch hole.

3.  Install the Badger Meter isolation valve and nipple 

onto the fitting using pipe thread sealant or Teflon® 
tape on all threads.

4.  Install the Badger Meter hex mounting adapter onto 

the valve assembly. Use pipe thread sealant on the 
adapter. Tighten the hex adapter so that no stud is 
aligned with the center-line of the pipe. This could 
interfere with final sensor alignment. Measure depth 
and set the height of the nuts of the hex mounting 
adapter.

5.  Open the bleed petcock valve on the hex adapter to 

relieve the pressure as the sensor tube is installed. 
Carefully hand insert the Badger Meter hot tap flow 
sensor tube into the hex mounting adapter. The 
sleeve should be inserted past the top two O-rings in 
the adapter (approx. 1 to 1-1/4 inches). 

Take care not 

to push the tube in too far as the impeller could be 
damaged if it strikes the closed valve.

6.  Even if the sensor is installed with system drained, 

Badger Meter recommends that a HTT, hot tap 
insertion/removal tool be purchased for future 
service. This tools allows the sensor tube assembly to 
be removed from the pipe line without draining the 
entire loop where the sensor is mounted.

7.  In a fully depressurized and drained pipe, the sensor 

tube assembly may be installed by hand. 

Carefully 

and very slowly

 open the isolation valve to relieve 

any pressure that may have built up. Fully open the 
isolation valve. Push the sensor tube into the pipe 
with a slight  twisting motion. Guide the sensor 
collar holes over the three hex adapter studs until 
the collar rests on the nuts. Hex nuts should have 
been previously set to the correct height. Install the 
three lock nuts onto these studs at the top of the 
positioning collar and securely tighten.

8.  Loosen the two set screws in the positioning collar 

with a 3/32 inch Allen wrench. Align the sensor 
sight holes along the pipe axis using the alignment 
rod provided in the installation kit supplied with 
the sensor. Ensure that the flow label arrow on the 
sensor matches the liquid flow direction inside the 
pipe. Tighten the positioning collar set screws. Note: 
As a backup to the flow label arrow, there is a small 
hole located beside one of the sighting holes to also 
indicate the upstream side of the sensor.  

INSTALLATION INTO A 
PRESSURIZED PIPELINE USING 
MODEL HTT

For information on installing hot tap sensor with older 
225H consult technical bulletin DID-001.

For pipe sizes 2½” and above; all Badger Meter sensors 
are inserted 1 1/2” from the inside wall of the pipe. The 
insertion depth is controlled by the position of the hex 
nuts on the three threaded rods. The formula below 
defines the distance between the top of the sensor hex 
mounting adaptor and the bottom of the positioning 
collar (the top of the hex nut). Reference Figure 3.

D = 16 3/8” - ( H + Pipe Wall Thi 1.5 “ )

Example:  If sensor is installed in a 8 inch Sch 80 pipe with 
a pipe wall thickness of 1/2 inch and the “H” dimension is 
10 inches then the calculation would be as below:

D = 16 3/8 - ( 10 0.5 1.5 inches)
D =  4 3/8”

BLEED VALVE

HEX NUT

JAM NUT

Figure 3:  

Page 5 

August 2012

Summary of Contents for 220BR

Page 1: ...Series 200 Insertion Style Flow Sensors Installation Operation Manual 872020 EN August 2012 Rev 8 IMPORTANT This manual contains important information READ AND KEEP FOR REFERENCE...

Page 2: ...and 226SS 4 If the Pipe is Depressurized and Drained 5 INSTALLATION INTO A PRESSURIZED PIPELINE USING MODEL HTT 5 ELECTRICAL INSTALLATION STANDARD SENSORS 6 ELECTRICAL INSTALLATION IR SENSORS 6 ELECTR...

Page 3: ...eter impeller flow monitor or transmitter Badger Meter non magnetic flow sensors provide an accurate rate of liquid flow as well as total accumulated flow A number of sensor models are offered which c...

Page 4: ...ure removal of sensor for service or cleaning if necessary HOT TAP INSTALLATION FOR 225BR 226BR AND 226SS Badger Meter Series 200 hot tap style liquid flow sensors are designed for use in cases where...

Page 5: ...flow sensor tube into the hex mounting adapter The sleeve should be inserted past the top two O rings in the adapter approx 1 to 1 1 4 inches Take care not to push the tube in too far as the impeller...

Page 6: ...wo remaining lock nuts down until they just contact the positioning collar Do not tighten at this time 8 Remove the Model HTT Insertion Removal Tool by loosening the two thumbscrews removing the clevi...

Page 7: ...or transmitter locate the section of terminal strip on the monitor labeled SENSOR INPUT or SENSOR Connect the red wire to IN SIGNAL or SIGNAL terminal and the black wire to GND SIGNAL or COM terminal...

Page 8: ...Series 200 Flow Sensors Page 8 August 2012...

Page 9: ...ndards Columns 4 and 5 The K value and Offset that should be used in our frequency equation Freq Gpm K Offset This equation describes the frequency of the output signal of all Badger Meter flow sensor...

Page 10: ...8 071 41 063 0 283 80 2 500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2 500 Sch 60 8 625 7 813 38 288 0 279 80 2 500 Extra Strong Sch 80 8 625 7 625 36 315 0 276 80 2 500 PVC Class 125 8 625 8 095 41...

Page 11: ...11 400 12 000 22 inch Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sch 80 22 00 19 75 259 513 0 573 500 15 000 24 inch Std Wt Sch 20 24 0...

Page 12: ...tion the impeller in the cavity oriented as in step 4 so that the impeller blades point into the flow direction and toward the small alignment hole located beside one of the sighting holes on metal se...

Page 13: ...00 hex adapter valve bronze UNS C83600 Sensor Sleeve and Hex Adapter for 220SS and 226SS Series 300 stainless steel Temperature Ratings Standard version 2210F 1050C continuous service High temperature...

Page 14: ...Series 200 Flow Sensors This page intentionally left blank Page 14 August 2012...

Page 15: ...Installation Operation Manual This page intentionally left blank Page 15 August 2012...

Page 16: ...6 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East a...

Reviews: