Badger Meter 220BR Installation & Operation Manual Download Page 13

Installation & Operation Manual

2.  If you suspect that the sensor is bad, you can test the 

monitor circuitry by connecting a piece of wire to one 
of the sensor input terminals and tap the other side of 
the wire to the other sensor input terminal. Shorting 
across the sensor input terminals ON and OFF 
repeatedly allows the display to respond by trying 
to calculate a flow rate for the frequency of your 
shorting action. If the display does not show a change 
from 0.00, it indicates a problem with the monitor.

3.  If the monitor tests ok and there are any splices in the 

cable, break the sensor cable at the splice closest to 
the sensor and retry the shorting test in step 2.

4.  If the cable tests ok, drain the pipe line, verify the 

pressure is off, remove top lock nuts holding the 
sensor electronics. Spin the impeller by hand. If flows 
are noted  on the display, and impeller spins freely 
then the flow rates may have been below our design 
minimums or the line was full of air. Try again. If the 
sensor fails to respond then replace sensor.

SPECIFICATIONS

Wetted Materials for all sensors

• 

See Technical Brief for material specifics

 

Sensor Sleeve and Hex Adapter for 220BR, 225BR, and

226BR

• 

Sleeve: admiralty brass, UNS C44300; hex adapter: 
valve bronze, UNS C83600

Sensor Sleeve and Hex Adapter for 220SS and 226SS

• 

Series 300 stainless steel

Temperature Ratings

• 

Standard version: 2210F (1050C) continuous service

• 

High temperature version: 2850F (140.60C) continuous 
service; 3050F (1500C) peak temperature (limited 
duration)

Pressure Ratings

 At 1000F

At 3000F

220SS

400 psi

325 psi

220B

400 psi

325 psi

225B

300 psi

210 psi

226B

400 psi

250 psi

226SS

400 psi

300 psi

  

 

 

 

     

 

Recommended Design Flow Range

• 

0.5 to 30 ft/sec

• 

Initial detection below 0.3 ft/sec

Accuracy

• 

± 1.0% of full scale over recommended design flow 
range

Repeatability

• 

± 0.3% of full scale over recommended design flow 
range

Linearity

• 

± 0.2% of full scale over recommended design flow 
range

Transducer Excitation

• 

Quiescent current  600uA@8VDC to 35VDC max.

• 

Quiescent voltage (V

high

 

Supply Voltage -(600uA*Supply impedance)

• 

ON State (V

Low

)  Max. 1.2VDC@40mA current limit 

(15ohm+0.7VDC)

Output Frequency

• 

3.2 Hz to 200 Hz

Output  Pulse Width

• 

5 msec ±25%

Electrical Cable for Standard Sensor Electronics

• 

20 feet of 2-conductor 20 AWG shielded U.L. type 
PTLC wire provided for connection to display or 
analog transmitter unit.  Rated to 1050C. May be 
extended to a maximum of 2000 feet with similar 
cable and insulation appropriate for application.

Electrical Cable for IR Sensor Electronics

• 

48 inches of U.L. Style 116666 copper solid AWG 18 
wire with direct burial insulation.  Rated to 1050C.

Page 13 

August 2012

Summary of Contents for 220BR

Page 1: ...Series 200 Insertion Style Flow Sensors Installation Operation Manual 872020 EN August 2012 Rev 8 IMPORTANT This manual contains important information READ AND KEEP FOR REFERENCE...

Page 2: ...and 226SS 4 If the Pipe is Depressurized and Drained 5 INSTALLATION INTO A PRESSURIZED PIPELINE USING MODEL HTT 5 ELECTRICAL INSTALLATION STANDARD SENSORS 6 ELECTRICAL INSTALLATION IR SENSORS 6 ELECTR...

Page 3: ...eter impeller flow monitor or transmitter Badger Meter non magnetic flow sensors provide an accurate rate of liquid flow as well as total accumulated flow A number of sensor models are offered which c...

Page 4: ...ure removal of sensor for service or cleaning if necessary HOT TAP INSTALLATION FOR 225BR 226BR AND 226SS Badger Meter Series 200 hot tap style liquid flow sensors are designed for use in cases where...

Page 5: ...flow sensor tube into the hex mounting adapter The sleeve should be inserted past the top two O rings in the adapter approx 1 to 1 1 4 inches Take care not to push the tube in too far as the impeller...

Page 6: ...wo remaining lock nuts down until they just contact the positioning collar Do not tighten at this time 8 Remove the Model HTT Insertion Removal Tool by loosening the two thumbscrews removing the clevi...

Page 7: ...or transmitter locate the section of terminal strip on the monitor labeled SENSOR INPUT or SENSOR Connect the red wire to IN SIGNAL or SIGNAL terminal and the black wire to GND SIGNAL or COM terminal...

Page 8: ...Series 200 Flow Sensors Page 8 August 2012...

Page 9: ...ndards Columns 4 and 5 The K value and Offset that should be used in our frequency equation Freq Gpm K Offset This equation describes the frequency of the output signal of all Badger Meter flow sensor...

Page 10: ...8 071 41 063 0 283 80 2 500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2 500 Sch 60 8 625 7 813 38 288 0 279 80 2 500 Extra Strong Sch 80 8 625 7 625 36 315 0 276 80 2 500 PVC Class 125 8 625 8 095 41...

Page 11: ...11 400 12 000 22 inch Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sch 80 22 00 19 75 259 513 0 573 500 15 000 24 inch Std Wt Sch 20 24 0...

Page 12: ...tion the impeller in the cavity oriented as in step 4 so that the impeller blades point into the flow direction and toward the small alignment hole located beside one of the sighting holes on metal se...

Page 13: ...00 hex adapter valve bronze UNS C83600 Sensor Sleeve and Hex Adapter for 220SS and 226SS Series 300 stainless steel Temperature Ratings Standard version 2210F 1050C continuous service High temperature...

Page 14: ...Series 200 Flow Sensors This page intentionally left blank Page 14 August 2012...

Page 15: ...Installation Operation Manual This page intentionally left blank Page 15 August 2012...

Page 16: ...6 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East a...

Reviews: