Badger Meter 220BR Installation & Operation Manual Download Page 4

Series 200 Flow Sensors

3 ¾”

2

03

4

5

Adjusting Nuts

Figure 1:  Installation for 220BR and 220SS

3.  Clean O-rings and flow sensor sleeve, and lightly 

lubricate O-rings with silicone grease from the packet 
provided or some other acceptable lubricant. Take 
care not to get grease on the impeller or bearing.

4.  Insert the flow sensor into the 2 inch NPT adapter so 

that the mounting holes in the positioning collar fit 
over the studs on the adapter. Lower the sensor onto 
the previously adjusted nuts. Install the lock nuts on 
top of the positioning collar and tighten. Now tighten 
the lower jam nuts firmly against the upper adjusting 
nuts to secure them for future removal of the sensor 
for inspection or service.

Alignment of Flow Sensor

1.  Loosen positioning collar set screws with a 3/32 inch 

Allen wrench. Place the alignment rod through the 
sight holes in the flow sensor. Refer to Figure 2. Using 
the alignment rod as a guide, align the flow sensor so 
that the flow label arrow matches pipe flow direction 
and so that the alignment rod is exactly parallel to the 
pipe. This procedure aligns the impeller directly into 
the fluid flow.

SET SCREW

ALIGNMENT ROD

ALIGNMENT ROD

C

C

Figure 2:  Alignment of Flow Sensor in 220BR and 

220SS

2.  As a backup to the flow arrow label, there is a 

small hole next to the larger sighting hole of the 
upstream side. With a 3/32 inch Allen wrench, tighten 
positioning collar set screws.

3.  Double check that the sighting holes in the sleeve are 

parallel down the pipe and that the flow arrow label 
matches pipe liquid flow direction.

4.  Cable routing: The positioning collar is threaded for 

connection of a standard 1/2 inch electrical conduit 
(flex cable) or a wire strain relief.  Route cable as 
required. Be sure to leave enough flex in cable or 
conduit to allow future removal of sensor for service 
or cleaning if necessary. 

HOT TAP INSTALLATION FOR 
225BR, 226BR, AND 226SS

Badger Meter Series 200 hot tap style liquid flow sensors 
are designed for use in cases where pipelines will be in 
continuous service and depressurizing or draining the 
system for installation or service is not practical.

The Series 200 hot tap sensors are designed to be installed 
either in a depressurized pipe by hand or “Hot Tapped” 
into a pressurized pipeline. Both installation procedures 
are listed in this installation and operation manual. If 
there is the slightest possibility that the pipe could be 
full or pressurized, 

FOLLOW THE INSTALLATION FOR 

PRESSURIZED PIPE.

Refer to Figure 3 for location or identification of the 
various parts described in the following procedures.

The insertion depth and alignment of the sensor assembly 
are critical to the accuracy of the flow measurement. The 
flat end of the sensor tube assembly 

MUST BE INSTALLED

1-1/2 inches from the inside wall of the pipe. In order to 
allow for variations in wall thickness, lining or coatings 
the depth adjustment is controlled by the position of the 
hex nuts on the three threaded studs of the hex mounting 
adapter. The hex mounting adapter is provided with a 
2 inch male NPT connection. Both gate and ball valve 
units are provided with 2 inch nipples for mounting onto 
saddles, weld-o-lets, etc.

Depth setting is accomplished by positioning the hex 
nuts 14-7/8 inches minus the thickness of the pipe, from 
the outside diameter of the pipe. For example, measure 
the wall thickness of the pipe from the coupon removed 
when the 1-7/8 inch hole was cut into the pipe. If the pipe 
was 1/8 inch thick, subtract 1/8 inch from 14-7/8 inch, or 
position the nuts 14-3/4 inch from the outside diameter of 
the pipe. This will allow the 16-3/8 inch sensor to protrude 
1-1/2 inch into the pipe.

Apply anti-seize thread lubricant,  supplied with the 
sensor, to the threaded studs of the mounting adaptor.

Page 4

 

August 2012

Summary of Contents for 220BR

Page 1: ...Series 200 Insertion Style Flow Sensors Installation Operation Manual 872020 EN August 2012 Rev 8 IMPORTANT This manual contains important information READ AND KEEP FOR REFERENCE...

Page 2: ...and 226SS 4 If the Pipe is Depressurized and Drained 5 INSTALLATION INTO A PRESSURIZED PIPELINE USING MODEL HTT 5 ELECTRICAL INSTALLATION STANDARD SENSORS 6 ELECTRICAL INSTALLATION IR SENSORS 6 ELECTR...

Page 3: ...eter impeller flow monitor or transmitter Badger Meter non magnetic flow sensors provide an accurate rate of liquid flow as well as total accumulated flow A number of sensor models are offered which c...

Page 4: ...ure removal of sensor for service or cleaning if necessary HOT TAP INSTALLATION FOR 225BR 226BR AND 226SS Badger Meter Series 200 hot tap style liquid flow sensors are designed for use in cases where...

Page 5: ...flow sensor tube into the hex mounting adapter The sleeve should be inserted past the top two O rings in the adapter approx 1 to 1 1 4 inches Take care not to push the tube in too far as the impeller...

Page 6: ...wo remaining lock nuts down until they just contact the positioning collar Do not tighten at this time 8 Remove the Model HTT Insertion Removal Tool by loosening the two thumbscrews removing the clevi...

Page 7: ...or transmitter locate the section of terminal strip on the monitor labeled SENSOR INPUT or SENSOR Connect the red wire to IN SIGNAL or SIGNAL terminal and the black wire to GND SIGNAL or COM terminal...

Page 8: ...Series 200 Flow Sensors Page 8 August 2012...

Page 9: ...ndards Columns 4 and 5 The K value and Offset that should be used in our frequency equation Freq Gpm K Offset This equation describes the frequency of the output signal of all Badger Meter flow sensor...

Page 10: ...8 071 41 063 0 283 80 2 500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2 500 Sch 60 8 625 7 813 38 288 0 279 80 2 500 Extra Strong Sch 80 8 625 7 625 36 315 0 276 80 2 500 PVC Class 125 8 625 8 095 41...

Page 11: ...11 400 12 000 22 inch Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sch 80 22 00 19 75 259 513 0 573 500 15 000 24 inch Std Wt Sch 20 24 0...

Page 12: ...tion the impeller in the cavity oriented as in step 4 so that the impeller blades point into the flow direction and toward the small alignment hole located beside one of the sighting holes on metal se...

Page 13: ...00 hex adapter valve bronze UNS C83600 Sensor Sleeve and Hex Adapter for 220SS and 226SS Series 300 stainless steel Temperature Ratings Standard version 2210F 1050C continuous service High temperature...

Page 14: ...Series 200 Flow Sensors This page intentionally left blank Page 14 August 2012...

Page 15: ...Installation Operation Manual This page intentionally left blank Page 15 August 2012...

Page 16: ...6 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East a...

Reviews: